NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
190
11/04 MN01219002Z-EN
DPV1 error messages
The NZM-XDMI-DPV1 generates the DPV1 error messages
contained in the following table.
Table 55: DPV1 error messages
Error message
Meaning
Clarification/Hint
Access denied
(Code B6
hexadecimal)
The accessed object is
inhibited for the type of the DP
master
You have accessed an object with a class 1
DP master which can only be accessed by a
class 2 DPV1 master.
Please note the object description.
The accessed object is
inhibited for the selected
service
You have either attempted to access an
object with a Write service which is read-
only, or have attempted to access an object
with a Read service which is write-only.
Please note the object description.
Feature not
supported
(Code A9
hexadecimal)
During writing of the “DMI
output assignment” you have
selected a parameterization for
the motor-starter function
even though the connected
circuit-breaker does not
support it
Please note the object description.
You have issued a command
when writing the “circuit-
breaker/DMI commands“
object which requires a remote
operator or motor-starter
function, even though this is
not parameterized
Please note the object description.
Invalid index
(Code B0
hexadecimal)
The index defined in the Read
or Write service is invalid for
the NZM-XDMI-DPV1
Use the Index defined in the object
description