Engineering and installation
25
11/04 MN01219002Z-EN
X
Fasten the cable also to one of the straps provided on the
circuit-breaker.
X
Connect both of the auxiliary switches to the NZM:
– Input 4 of the DMI is connected to the auxiliary switch
for trip release recognition (tripped = L, not tripped =
H),
– Input 5 of the DMI is connected to the auxiliary switch
for ON/OFF detection (ON = H, OFF = L).
The circuit-breaker and DMI will exchange data within 5 s of
connecting the cable at both ends. All the available
parameters and data can then be interrogated as required.
h
For further information refer to the relevant
documentation for the individual NZM types as this varies
according to the type and model concerned.