Parameter setting
55
11/04 MN01219002Z-EN
Three different methods are used depending on the versions
of the DMI and communication modules involved:
DMI with any Firmware version and DP module with
Firmware versions < V1.10
X
Check that there is no bus communication.
Only then can the address be entered.
X
Select 0XYZ using the cursor buttons < or >.
X
Change the individual values using the cursor buttons
Í
or
Ú
.
An address change is no longer possible if the fieldbus is
active. The address can only be displayed for verification
purposes.
X
Confirm your selection by pressing
OK
.
DMI Firmware version < V1.2.1 and DP module with
Firmware version
f
V1.10
This message informs you that you have a DMI and
communication module Firmware version which are
incompatible with one another.
X
Use the NZM-XPC-Soft to install a Firmware version
f
V1.2.1 on the DMI.
The most up-to-date versions are available on the Internet
a
http://www.eaton.com/moeller
→
Support,
Serarch term: DMI.
DP-DEVICE
STATION
ADDRESS 0XYZ
Caution!
If you check the address during communication, the
outputs of the DMI cannot be controlled by the bus master
for the duration of this process. Switched outputs turn to
“OFF” and only change back to “ON” when 3 to
5 seconds have elapsed after exiting the address display.
The input values are not updated during this time.
pls. Update
DMI Software
to V1.2.1
or higher