DMI
56
11/04 MN01219002Z-EN
DMI Firmware version
f
V1.2.1 and DP module with
Firmware version
f
1.10
After you have selected the “Address” submenu the
message indicated opposite will appear on the display. The
display also appears if you connect a new (not yet
addressed) communication module.
The fourth line contains a 4 digit numeric input/display field
for the address. If the DMI has been assigned with the DP
address beforehand, the current address will be displayed. If
the devices are still in the default (ex-works) state the
address 0126 will be displayed. The cursor will flash on the
thousand digit in both cases.
Assignment of a valid address:
X
Use the < or > cursor buttons on the individual positions.
X
Change the individual values using the cursor buttons
Í
or
Ú
.
X
Confirm your selection by pressing
OK
.
The set value is transferred to the module.
If the address input has been successful, the following
message appears:
The message will be displayed for a maximum of 5 s or until
the
ESC
or
OK
buttons are pressed. The previous selection
menu will then be redisplayed.
The following faults can occur when entering the
address:
If a communication module or a module with the “Point-to-
Point” type code is not connected to the DMI when the
“Address” submenu is accessed, the fault message
indicated opposite is shown on the display.
Module
Profibus-DP
Address
0XYZ
Module
Value
Address
Accepted
No
Network
Module
Available
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com