Operating the device
83
11/04 MN01219002Z-EN
BUS LED, function
Figure 19: BUS LED function display
a
LED continuously lit:
PROFIBUS-DP communication in order
b
LED flashes:
No PROFIBUS-DP communication ongoing
Commissioning the
PROFIBUS-DP line with
NZM-XDMI-DPV1
GSD file
The “Moel4D11.gsd” GSD file is necessary for selection of
the device with the configuration of the PROFIBUS-DP line
and operation of the bus. You can download the most up-to-
date version at the following Internet address:
http://www.eaton.com/moeller
→
Support
Follow the links on these pages.
The following modules are defined for the NZM-XDMI-DPV1
in the GSD for cyclic data exchange:
• Module 1: Circuit Breaker Profile 1: 3 Byte inputs/
2 Byte outputs,
• Module 2: Circuit Breaker Profile 2: 11 Byte inputs/
2 Byte outputs,
• Module 3: Circuit Breaker Profile 1 and motor starter:
4 Byte inputs/3 Byte outputs,
• Module 4: Circuit Breaker Profile 2 and motor starter:
12 Byte inputs/3 Byte outputs,
The meaning of the data of the respective format
a
section “PROFIBUS-DPV0 functions”, Page 85.
b
a