NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
92
11/04 MN01219002Z-EN
Format of the data inputs
Reading of the data inputs is implemented directly via the
DPV0 read commands or via the input bytes of the DP master
defined by the PROFIBUS-DP configuration. Note the
documentation of the master device for this purpose. Eleven
Octets are read as data inputs which contain the following
data:
Table 9:
Address assignment of the module 2 data inputs
Data position
Designation
Octet 1
Bit 0 and Bit 1
Circuit-breaker position
Bit 2 and Bit 3
Circuit-breaker state
Bit 4
Ready to switch on
Bit 5 and Bit 6
Not used
Bit 7
Overload warning
Octet 2
Bit 0
Not used
Bit 1
General warning
Bit 2
Not used
Bit 3
Input 0
Bit 4 to Bit 6
Trip cause (Release reason)
Bit 7
Load rejection prewarning
Octet 3 and 4
I
1
Octet 5 and 6
I
2
Octet 7 and 8
I
3
Octet 9 and 10
I
max
Octet 11
Bit 0
Input 1
Bit 1
Input 2
Bit 2
Input 3