Emergency On Call Service: Local representative (
www.eaton.eu/aftersales
) or +49 (0) 180 5 223822 (de, en)
9/9
11
/15
IL
01206
006Z
Eaton Industries GmbH, Hein-Moeller-Straße 7-11, 53115 Bonn, Germany
© 2000 by Eaton Industries GmbH,
www.eaton.eu/documentation
All Rights Reserved
11/15 IL01206006Z
10045159
DHW
Printed in Germany (12/15)
Mounting – Montage – Montage – Montaje – Montaggio –
安
安装
装
–
Монтаж
Wiring terminations circuit breaker type NZM…2…-NA (CNA)
Wiring terminations molded case switch type N(S)2…-NA
Insulating plate, Cat. No. IPXXX
Mounting of insulating plate IPXXX, (shown shaded in the diagram)
is required on UL/CSA labeled models for all installations in which the
Line Voltage exceeds 480 V.
Mount as shown in diagram.
Connector
Wire size
Wire
Max.
Tightening-
Type
75° C
A-Rating
Torque
NZM4-XKC
1 x AWG 12 – 350 kcmil
Cu only
250
14 Nm (124 lb-in)
5 Nm (44 lb-in)
(AWG10)
NZM4-XKA
1 x AWG 6 – 350 kcmil
Cu only
250
30 Nm (265 lb-in)
1) NZM4-XKS
1 x AWG 12 – 350 kcmil
Cu only
250
14 Nm (124 lb-in)
2) Integrated
Auxiliary
Terminal
1 x AWG 12 – 18
Cu only
1.2 Nm (11 lb-in)
1) Connector Pads Type NZM2-XKS for Compression Crimp lugs supplied standard on all NZM2
circuit breakers and switches.
2) Integrated Auxiliary Terminal on Barrel (Tunnel) Mechanical lug Connector Type NZM2-XKA only.
NZM...2...-NA
NZM...2...-CNA
N(S)2...-NA
> 480 V:
ON
Trip
Z 2
1.7 Nm
(15 lb-in)
4 x M4 x 85/20
3
2
2
1
NZM.2-4-...
NZM.2-...
70 mm
(2.8”)
35 mm
(1.4”)
145
mm
(5.7”)
4 x M4 x 85/20
1.7 Nm