5. Site Requirements For Standard Enclosures
Enclosure Space Requirements
Select a location for the enclosure that will provide adequate room for opening doors and side panels, and
operating and servicing slide-out electronic products. The enclosure must be positioned so that there is un-
restricted air movement for all ventilated surfaces.
Enclosure Dimensions
Enclosure heights: 77.00”, 84.00” and 96.00”
Enclosure width:
24” wide rack: 24.00”
30” wide rack: 30.00”
48” wide rack: 48.00 inches
(no additional width is gained when ganging racks together)
Side Panels: add .56” (9/16”) to the enclosure width for each Side Panel
Enclosure frame depths without doors: 34.50” and 39.25” (excluding trim)
Enclosure depth with doors: 40.06” and 44.80” (includes door handles)
Floor Loads
Each enclosure bay, when loaded to its maximum capacity, can weigh up to 2500 lbs. (The actual weight can
vary somewhat, depending on the actual component selection.) Each enclosure bay is supported on four
leveling glides. Each glide has a floor contact area of 1.1 square inch.
WARNING: IT IS THE CUSTOMER’S RESPONSIBILITY TO ENSURE THAT THE FLOOR HAS A
STRUCTURAL LOAD CAPACITY THAT WILL SAFELY BEAR THE WEIGHT OF THE PARAMOUNT
ENCLOSURE SYSTEM.
Pub Num: MN159002EN rev1.0
Paramount Enclosure
Installation Guide