28
Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P-164001108—Rev 01
Figure 20. Modem Setup Screen
Touch
Set #1
to enter the number for destination 1. If dialing out with a 9, add commas to pause the modem
slightly before it dials the outside number.
Set #2
lets you set a second number.
Toggle
Use
to a green check mark to enable the number.
Toggle
Data
to a green check mark to send data to a pager. Add commas after the telephone number (to pause
the modem) and then add numbers to be sent to a pager. The data in the
Modem
field for dial-out number 1 or
2 will have this format:
9,,,8045551212,,,579802(Dial out code/commas to pause modem/pager number/commas to pause modem/
numeric data to be sent to pager)
After numbers are set up, toggle
Send Modem Alarms
to a green check mark to enable sending a summary
alarm via modem.
To test the modem dial out feature, touch
Dial 1
or
Dial 2
to force the modem to dial number 1 or 2.
Touch
Reset
to reset the modem.
44..55
O
Otthheerr S
Sccrreeeennss
These screens are not for customer use:
•
Config
tab: the
Configuration
screen (
) is setup by Eaton at the factory and requires Eaton
authorization to make changes, but any user can view the screen. Eaton uses the
Configuration
screen to
describe the system to the display software. Touch the
Config
button to view. The screen must be
configured as shown.
Summary of Contents for PDI WaveStar BCMS
Page 1: ...p n P 164001108 Revision 01 Installation and Operation Manual Eaton PDI WaveStar BCMS Hub...
Page 4: ......
Page 10: ...2 Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P 164001108 Rev 01 Safety...
Page 52: ...44 Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P 164001108 Rev 01 Glossary...
Page 54: ...P 16400110801 P 164001108 01...