Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01
11
C
Chhaapptteerr 44 C
Cuussttoom
meerr S
Seennssoorr B
Booaarrdd C
Coonnnneeccttiioonnss
All sensor board connections internal to the monitored unit are made in manufacturing. However, any external
sensor board connections must be made during installation. These connections typically are limited to the
following connections, which are made to sensor boards in the Monitoring Compartment:
•
Remote Emergency Power Off (REPO)
•
Local digital input connections, such as building alarms
•
Local relay output connections, such as a summary alarm
44..11
S
Seennssoorr TTyyppeess
To monitor your system, Infinity has a variety of sensors including:
•
Voltage sensor for (1) source, 3-Phase + Neutral ≤ 660Vac.
•
Current sensor for (1) source 3-Phase + N Ground.
•
Panelboard Sensor Strips with solid core 100A CTs for monitoring panelboard circuits (
).
•
Transformer Sensor, monitoring (2) temperatures (high-temp and over-temp).
•
Digital Inputs Option Board, monitoring up to (8) digital inputs, such as circuit breaker aux contacts and
building alarms.
•
Relay Option Board with (4) relay outputs.
Figure 5. Panelboard with Sensor CT Strips on Each Side
Summary of Contents for PDI WaveStar Infinity 2