Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01
45
Limits are not set by panelboard but by sensor strip. As shown in
, there are separate sensor strips for
both the odd-numbered and even-numbered sides of a 42-circuit panelboard. For 84-circuit panelboards, you
must set limits for four (4) sensor strips.
You must be logged in (as administrator) to set panelboard
Limits
.
A
Appppllyyiinngg IIddeennttiiccaall P
Paarraam
meetteerrss ffoorr A
Allll C
Ciirrccuuiittss
On the
LIMITS
screen, select a panelboard sensor strip from the
Sensors
drop-down list.
To set the same values for all circuits monitored by the sensor strip, check
All
and fill in the correct values in
the first column.
Figure 33. Panelboard Sensor Strip, Applying the Same Parameters to All Circuits
You should specify
Circuit Breaker (CB) size
,
default = 20A
Warning Threshold
(
W.
Thresh.
) as percent of CB size
default = 70.
Alarm Threshold
(
A. Thresh.
)
as percent of CB size,
default = 80.
Warning Time
(W. Time)
in
seconds: the circuit must
exceed the Warning Threshold
for the speci
�
ied time to
declare a warning (default = 5
sec.)
Alarm Time (A. Time)
in
seconds: the circuit must
exceed the Alarm Threshold
for the speci
�
ied time to
declare an alarm (default = 5
sec.)
Check
Warning
,
Alarm
, and/or
Zero
boxes if you want these alerts to be
issued.
If you do not check its box, the alarm
will not be issued even if you speci
�
ied a
threshold.
C
Cuussttoom
miizziinngg A
Allaarrm
m P
Paarraam
meetteerrss bbyy C
Ciirrccuuiitt
If you do not check
All
, values can be changed individually by circuit.
You can set typical circuit parameters using
All
, then specify parameters for individual circuits as needed.