AlArm pull stAtion - pH1

   TM230 Issue F   July 2019   www.eaton.com

Alarm pull station - PH1

English

1.0 Introduction

These manual fire alarm pull stations have been designed 

for use in hazardous locations and harsh environmental 

conditions. The GRP enclosures are suitable for use 

offshore or onshore where light weight combined with a 

high level of corrosion resistance is required.

2.0 General safety messages and 

warnings

All instructions and safety messages in this manual must 

be followed to allow safe installation of the device. The 

device must only be installed and maintained by correctly 

trained site personnel/installers.

I.  To reduce the risk of ignition of hazardous 

atmospheres and shock, do not apply power to the 

device until installation has been completed and the 

device is fully sealed and secured.

II.  To reduce the risk of ignition of hazardous 

atmospheres and shock, keep device tightly closed 

when the circuit is energised.

III.  Before removing the cover for installation or 

maintenance, ensure that the power to the device 

is isolated.

IV.  Following installation, test the device to ensure 

correct operation.

V.  Following installation ensure a copy of this manual is 

made available to all operating personnel.

VI.  When installing the device, requirements for 

selection, installation and operation should be 

referred to e.g. IEE Wiring Regulations and the 

‘National Electrical Code’ in North America. Additional 

national and/or local requirements may also apply.

VII.  Cable termination should be in accordance with 

specification applying to the required application. 

MEDC recommends that all cables and cores should 

be correctly identified. Please refer to the wiring 

diagram in this manual (or separate diagram provided 

with the unit).

VIII. Ensure that only the correct listed or certified cable 

glands are used and that the assembly is shrouded 

and correctly earthed.

IX.  Ensure that only the correct listed or certified 

stopping plugs are used to blank off unused gland 

entry points and that the NEMA/IP rating of the unit 

is maintained.

X.  MEDC recommend the use of a sealing compound 

such as HYLOMAR PL32 on the threads of all glands 

and stopping plugs in order to maintain the IP rating 

of the unit.

XI.  The internal earth terminal, where fitted, must be 

used for the equipment grounding and the external 

terminal, if available, is for a supplementary bonding 

connection where local codes or authorities permit or 

require such a connection.

XII.  When installing the device, MEDC recommends the 

use of stainless steel fasteners. Ensure that all nuts, 

bolts and fixings are secure.

XIII. The pull station should not be mounted closer than 

40mm to any solid object which does not form part 

of the unit.

XIV. When fitting or removing cable entry glands, the 

cable entry inserts must be held with a suitable tool 

to prevent movement.

3.0 Installation

The unit is mounted via 4 off Ø6.5mm fixing holes in the 

base of the enclosure. The unit has been designed and 

certified to operate at any attitude.

The fixing holes have been designed to accept an M6 

screw or bolt.

Access to terminals

Unscrew the 4 off M6 screws (5.0mm A/F hexagon 

key) holding the cover assembly to the base. The cover 

screws are retained in the cover assembly for ease of 

installation. Gently lift the cover assembly away from the 

base of the enclosure to gain access to the interior.
Once termination is complete, carefully replace the cover 

assembly back onto the base of the enclosure, avoiding 

damage to the mating surfaces. Ensure the o-ring is 

correctly seated in its groove during re-assembly. Evenly 

tighten the 4 off M6 screws (5.0mm A/F hexagon key). 

Ensure the required gap (0.10mm Max.) is maintained 

between the cover and the base.

Summary of Contents for PH1

Page 1: ...Alarm pull station PH1 Technical manual...

Page 2: ...ULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT...

Page 3: ...Issue F July 2019 www eaton com Contents 1 0 INTRODUCTION 1 2 0 GENERAL SAFETY MESSAGES AND WARNINGS 1 3 0 INSTALLATION 1 Access to terminals 1 4 0 STANDARD WIRING OPTIONS 2 5 0 OPERATION 3 6 0 MAINT...

Page 4: ...iv Alarm pull station PH1 TM230 Issue F July 2019 www eaton com...

Page 5: ...ure that only the correct listed or certified cable glands are used and that the assembly is shrouded and correctly earthed IX Ensure that only the correct listed or certified stopping plugs are used...

Page 6: ...1 If a different wiring layout has been specified when ordering the unit please see the separate diagram supplied with the unit EOL resistors should only be fitted to the last unit in a system Standar...

Page 7: ...nt 6 0 Maintenance During the working life of the unit it should require little or no maintenance GRP will resist attack by most acids alkalis and chemicals and is as resistant to concentrated acids a...

Page 8: ...el of corrosion resistance is required The function of the PH1 call point is to raise an alarm manually once verification of a fire or emergency conditions exists by operating the LIFT and PULL handle...

Page 9: ...5 Alarm pull station PH1 TM230 Issue F July 2019 www eaton com Alarm pull station PH1 English...

Page 10: ...shall comply with the requirement given in this Safety Manual and Technical Manual regarding all relevant functional safety aspects such as application of use installation operation maintenance proof...

Page 11: ...1 0 INTRODUCTION 8 2 0 MESSAGES ET AVERTISSEMENTS G N RAUX DE S CURIT 8 3 0 INSTALLATION 8 Acc s aux bornes 8 4 0 OPTIONS STANDARD DE C BLAGE 9 5 0 FONCTIONNEMENT 10 6 0 ENTRETIEN 10 7 0 CERTIFICATIO...

Page 12: ...r que les presses toupes sp cifi es ou certifi es et du bon rev tement et mise la terre de l assemblage IX S assurer de n utiliser que les bouchons obturateurs sp cifi s ou certifi s pour obturer les...

Page 13: ...sp cifi lors de la commande de l unit merci de se r f rer sch ma s par fourni avec l unit Ne monter des r sistances EOL que sur le dernier module d un syst me C blage standard commutateur d allumage...

Page 14: ...e de vie GRP r siste l attaque de la plupart des acides des produits chimiques et des alcalis ainsi qu aux acides et produits alcalins concentr s comme la plupart des produits m talliques Cependant da...

Page 15: ...e situation d incendie ou d urgence en actionnant les poign es SOULEVER et TIRER Les grandes poign es SOULEVER et TIRER en polyester renforc la fibre de verre n cessitent une double action pour d clen...

Page 16: ...12 Alarm pull station PH1 TM230 Issue F July 2019 www eaton com Alarm pull station PH1 Francais...

Page 17: ...technique et de s curit en ce qui concerne tous les aspects pertinents de la s curit fonc tionnelle l utilisation l installation le fonctionnement la maintenance les essais de s ret les valeurs nomin...

Page 18: ...HRUNG 15 2 0 ALLGEMEINE SICHERHEITS UND WARNHINWEISE 15 3 0 INSTALLATION 15 Zugang zu den Anschl ssen 15 4 0 STANDARD SCHALTPLANOPTIONEN 16 5 0 BETRIEB 17 6 0 WARTUNG 17 7 0 ZERTIFIZIERUNGEN ZULASSUNG...

Page 19: ...augruppe ummantelt und korrekt geerdet ist IX Achten Sie darauf ausschlie lich die korrekten gelisteten oder zugelassenen Verschlussstopfen zur Abdeckung nicht verwendeter Durchf hrungseing nge zu ver...

Page 20: ...andere Schaltplananordnung vereinbart finden Sie diese auf dem separaten Schaltplan der mit dem Ger t geliefert wurde EOL Widerst nde d rfen nur an das letzte Ger t eines Systems angebracht werden St...

Page 21: ...wenig oder sogar keinerlei Wartung ben tigen GFK ist best ndig gegen ber den meisten S uren Alkalien und Chemikalien und ist ebenso best ndig gegen ber konzentrierten S uren und Alkalien wie die meis...

Page 22: ...r hohen Korrosionsbest ndigkeit notwendig ist Der PH1 Feuermelder dient zum manuellen Ausl sen eines Alarms wenn ein Brand oder eine Gefahrensituation best tigt wurde Dazu m ssen die Griffe LIFT und P...

Page 23: ...19 Alarm pull station PH1 TM230 Issue F July 2019 www eaton com Alarm pull station PH1 Deutsch...

Page 24: ...ntr chtigt werden 1 Der Benutzer muss alle in diesem Sicherhe itshandbuch und technischen Handbuch enthaltenen Bedingungen erf llen z B Verwendungszweck Installa tion Betrieb Wartung Funktionspr funge...

Page 25: ...TRODU O 22 2 0 PRECAU ES E ADVERT NCIAS GERAIS DE SEGURAN A 22 3 0 INSTALA O 22 Acesso aos terminais 22 4 0 OP ES DE FIA O PADR O 23 5 0 FUNCIONAMENTO 24 6 0 MANUTEN O 24 7 0 CERTIFICA O APROVA ES 24...

Page 26: ...oduzido neste manual ou o esquema separado fornecido com a unidade VIII Certifique se de que sejam utilizados exclusivamente prensa cabos corretos enumerados ou certificados e que o conjunto fique bli...

Page 27: ...o especificado no momento da encomenda da unidade for diferente consulte o esquema separado fornecido com a unidade Os resistores de fim de linha EOL devem ser montados somente na ltima unidade de um...

Page 28: ...uco ou nenhuma manuten o O poli ster refor ado com fibra de vidro GRP resiste ao ataque da maioria dos cidos bases e produtos qu micos em geral sendo resistente a cidos e bases concentrados como a mai...

Page 29: ...ecess rios A fun o do ponto de chamada PH1 acionar um alarme manualmente caso seja verificada a exist ncia de uma condi o de emerg ncia ou inc ndio atrav s do manuseio das alavancas de LEVANTAR e PUXA...

Page 30: ...26 Alarm pull station PH1 TM230 Issue F July 2019 www eaton com Alarm pull station PH1 Portugu s...

Page 31: ...mprir os requisitos deste Manual de seguran a e do Manual t cnico levando em conta todos os aspectos de seguran a funcional como as aplica es de uso instala o opera o manuten o testes de comprova o li...

Page 32: ...tained in this document and to prices are reserved so are errors and omissions Only order confirmations and technical documentation by Eaton is binding Photos and pictures also do not warrant a specif...

Reviews: