Safety considerations
47
06/10 MN03402004Z-DE/EN
• The trip block’s failure rates at 60 °C ambient air
temperature and self-heating are:
– Failure rate of safe failures
– Failure rate of dangerous failures
– Failure rate of detected safe failures
– Failure rate of dangerous but detected failures
• For the basic device, the failure rates at an ambient air
temperature of 40 °C and of 60 °C are the same.
• The basic device’s failure rates at 60 °C ambient air
temperature and self-heating are:
– Failure rate of safe failures
– Failure rate of dangerous failures
– Failure rate of detected safe failures
– Failure rate of dangerous but detected failures
163 FIT = 1.63 x 10
-7
/h
740.2 FIT = 7.402 x 10
-7
/h
35.6 FIT = 3.56 x 10
-8
/h
491.6 FIT = 4.916 x 10
-7
/h
430.5 FIT = 4.305 x 10
-7
/h
724.5 FIT = 7.245 x 10
-7
/h
143 FIT = 1.43 x 10
-7
/h
428.4 FIT = 4.284 x 10
-7
/h