I.L. PG24836G-591H
Effective: November 1999
Efectivo: Noviembre 1999
Página 5
Page 5
All general purpose dry-type distribution transformers are designed to
meet NEMA ST-20 established sound levels. However, to minimize the
potential for sound transmission to surrounding structures and sound
reflection, follow these instructions:
1. Mount the transformer away from corners, walls or ceilings. For
installation which must be near a corner, use sound absorbing
materials on the walls and ceiling.
2. Use flexible conduit to make the connections to the transformers.
3. Locate the transformers as far away as possible from areas where
sound is objectionable.
7.
CONNECTING CABLES TO TRANSFORMER
TERMINATIONS
Any standard cable of the conductor size specified in N.E.C. Section
310 can be used. Recommended external cable should be rated 90ºC
(sized at 75% ampacity) for encapsulated designs and 75ºC for
ventilated designs. Connectors should be selected on the basis of the
type cable and cable size used to wire the specific transformer.
■
Remove access panels to wiring compartment.
■
Install conduit and wiring through sides and/or bottom of
transformer case into wiring compartment.
■
Top entry of cable should be avoided.
■
Clean all electrical joints.
■
Connect primary wiring first to correct terminal as shown on the
transformer nameplate.
■
Insulate any unused tap leads and verify tap connections are tight.
■
Energize unit and measure secondary voltage to verify correct
voltage.
■
De-energize primary circuit and connect secondary wiring to
terminations in accordance with nameplate wiring diagram.
■
Make sure all connections are tight.
■
Re-install access panels.
Grounding
As required by the National Electrical Code, connect a ground cable to
the transformer enclosure. The transformer core is grounded to
enclosure.
8.
ENERGIZATION AND OPERATION GUIDELINES
For ventilated designs only, if moisture is evident, the unit should be
dried out by placing it in an oven or by blowing heated air over it. The
temperature should not exceed 110º C (230ºF) to prevent damage to
wiring insulation.
When the tests and connections are complete, the transformer may be
energized.
Todos los transformadores de distribución tipo seco son diseñados
para cumplir con los niveles de sonido establecidos por NEMA, norma
ST-20. Aún así para minimizar la transmisión potencial de sonido y su
reflexión, siga estas instrucciones:
1. Monte el transformador alejado de esquinas, paredes y techos. En
caso contrario, use materiales absorbentes de sonido en las paredes
2. Use tubo conduit flexible para hacer las conexiones al
transformador.
3. Coloque la unidad lo más retirada posible de áreas en las que el
nivel de ruido sea un factor limitante.
7.
CONEXION DE CABLES A LAS TERMINALES
DEL TRANSFORMADOR
Puede usar cualquier cable conductor aislado, del calibre
especificado por N.E.C. o los códigos aplicables. El cable de uso
exterior recomendado debe ser para 90ºC (calculado al 75% de
ampacidad) en diseños encapsulados, y para 75ºC␣ en diseños
ventilados. Los conectores deberán seleccionarse de acuerdo al tipo y
al calibre del cable conductor utilizado en la conexión al
transformador específico.
■
Remueva los páneles o tapas de acceso al compartimiento de
alambrado.
■
Instale tubo conduit y el cableado por el fondo o los lados del
gabinete del transformador hacia el compartimiento de terminales.
■
Evite el acceso de cable por la parte superior del gabinete de
diseños ventilados.
■
Limpie todas las uniones eléctricas.
■
Conecte primero la sección primaria a la terminal correcta, según
se muestre en la placa de datos.
■
Aisle todo tap (derivación) sin usar y revise que los taps
conectados estén apretados.
■
Energice la conexión primaria y mida el voltaje en la sección
secundaria, verificando que sea el voltaje correcto.
■
Desenergice y prepare la conexión en la sección secundaria de
acuerdo al diagrama de la placa de datos.
■
Asegúrese que todas las conexiones han sido apretadas.
■
Reinstale los páneles o tapas de acceso al compartimiento de
conductores.
Conexión a tierra (potencial cero)
Conecte el cable de tierra física al gabinete del transformador, así
como lo requiere el N.E.C.. El núcleo del transformador ya ha sido
aterrizado al gabinete.
8.
GUIA DE ENERGIZADO Y OPERACION
Para diseños ventilados solamente: si existe humedad evidente,
seque la unidad ya sea dentro de un horno o soplando aire caliente
por ella. La temperatura no debe exceder 110
°
C (230
°
F) para
prevenir daños al alambrado.
Una vez probado el transformador y terminadas las conexiones, el
transformador puede ser energizado.
Summary of Contents for Pow-R-Line SPX0361126
Page 2: ......
Page 4: ......
Page 6: ......
Page 7: ...TAB 1 Switchboards ...
Page 8: ......
Page 10: ......
Page 11: ...Instruction Data ...
Page 12: ......
Page 37: ...Component Data ...
Page 38: ......
Page 43: ......
Page 44: ......
Page 48: ......
Page 66: ...3 6 IM02601001E www eaton com Mechanical Installation ...
Page 114: ...14 IM02601001E www eaton com Using the I O Option Cards ...
Page 134: ...9 14 IM02601001E www eaton com Functions on the Web Server Pages Events Page ...
Page 156: ...10 22 IM02601001E www eaton com Setup on the Web Server Pages ...
Page 166: ...A 2 IM02601001E www eaton com Navigation Maps Main Menu Screens Sheet 1 ...
Page 167: ...www eaton com IM02601001E A 3 Navigation Maps Operating Mode Screens Sheet 2 ...
Page 168: ...A 4 IM02601001E www eaton com Navigation Maps Reset Mode Screens Sheet 3 ...
Page 169: ...www eaton com IM02601001E A 5 Navigation Maps Configuration Mode Screens Sheet ...
Page 170: ...A 6 IM02601001E www eaton com Navigation Maps ...
Page 172: ...B 2 IM02601001E www eaton com DIP Switch Description ...
Page 240: ...C 68 IM02601001E www eaton com Modbus Register Maps ...
Page 241: ......
Page 242: ......
Page 259: ...Shop Drawings ...
Page 260: ......
Page 262: ......
Page 264: ......
Page 266: ......
Page 268: ......
Page 270: ......
Page 272: ......
Page 274: ......
Page 275: ...Date PDF Generated 10 19 2012 Page 1 of 1 ...
Page 276: ......
Page 278: ......
Page 280: ......
Page 282: ......
Page 284: ......
Page 286: ......
Page 288: ......
Page 289: ...TAB 2 Panelboards ...
Page 290: ......
Page 292: ......
Page 293: ...Instruction Data ...
Page 294: ......
Page 296: ......
Page 325: ...Spare Parts ...
Page 326: ......
Page 371: ...Drawings ...
Page 372: ......
Page 374: ......
Page 376: ......
Page 378: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 387: ...TAB 3 Dry Type Transformers ...
Page 388: ......
Page 390: ......
Page 391: ...Instruction Data ...
Page 392: ......
Page 401: ...Drawings ...
Page 402: ......
Page 404: ......
Page 405: ...TAB 4 Molded Case Circuit Breakers ...
Page 406: ......
Page 408: ......
Page 409: ...Instruction Data ...
Page 410: ......
Page 417: ...TAB 5 Safety Switches ...
Page 418: ......
Page 420: ......
Page 421: ...Instruction Data ...
Page 422: ......
Page 424: ......
Page 452: ......
Page 453: ...Spare Parts ...
Page 454: ......
Page 467: ...Drawings ...
Page 468: ......
Page 470: ......
Page 471: ...Item 001 Cat DH261FGK ...
Page 472: ......
Page 474: ......
Page 475: ...Item 002 Cat DH261FGK ...
Page 476: ......
Page 478: ......
Page 479: ...Item 003 Cat DH261FGK ...
Page 480: ......
Page 482: ......
Page 483: ...Item 004 Cat DH261FGK ...
Page 484: ......
Page 486: ......
Page 487: ...Item 09 Cat DH364NRK ...
Page 488: ......
Page 490: ......
Page 491: ...Item 011 Cat DH324NGK ...
Page 492: ......
Page 494: ......
Page 495: ...Item 013 Cat DH362FRK ...
Page 496: ......
Page 498: ......
Page 499: ...Item 015 Cat DH321NRK ...
Page 500: ......
Page 502: ......
Page 503: ...Item 017 Cat DH362FRK ...
Page 504: ......
Page 506: ......
Page 507: ...Itm 019 Cat DH221NGK ...
Page 508: ......
Page 510: ......
Page 511: ...Item 021 Cat DH361UGK ...
Page 512: ......
Page 513: ...TAB 6 Enclosed Control NEMA ...
Page 514: ......
Page 516: ......
Page 517: ...Instruction Data ...
Page 518: ......
Page 550: ......
Page 551: ......
Page 552: ......
Page 561: ......
Page 562: ......
Page 578: ......
Page 579: ...Drawings ...
Page 580: ......
Page 582: ......
Page 584: ......