6
Series NRX with PXR - Instructions for
Spring Release, Latch Check Switch,
and Motor Operator
EATON
www.eaton.com
Instruction Leaflet
IL0131088EN
Effective May 2015
Section 5: Removal of Latch Check Switch
from Spring Release
Proceed with the following five steps.
Step 1:
Remove the spring release from the breaker prior to removing
a latch check switch by performing Steps 1 through 3 of Section 3.
Step 2:
If the latch check switch is internally connected to the spring
release, unplug its connector from the 2-pin plug in the spring release.
Figure 12.
2-Pin Plug for LCS Connection
Step 2.
Step 3:
With the spring release positioned as shown, pull back on the
locking tab to unlock the latch check switch from the spring release.
Figure 13. Step 3.
Step 4:
Tilt the latch check switch back and lift to release and remove
it from the spring release.
Figure 14. Step 4.
Step 5:
If another latch check switch is to be installed in the spring
release, perform Steps 2 through 5 of Section 4. If not, just reinstall
the spring release by performing Steps 3 through 8 of Section 2.