Instructional Leaflet 

IL0131093EN

Effective January 2019

Instructions for secondary terminal blocks 

  

  

EATON

 www.eaton.com

Step 6: 

Repeat Steps 4 and 5 until all terminal blocks are 

mounted, and check to ensure they are positioned in the cor-

rect locations.  A small number terminal blocks would look as 

shown.

Figure 19. Step 6.

Step 7: 

Carefully put the terminal block alignment bracket 

back into position by sliding it back into the mounted terminal 

blocks.

Figure 20. Step 7.

Step 8: 

Push the terminal block alignment bracket over 

the posts located on the terminal block mounting bracket.  

Ensure the alignment bracket is fully seated.

Figure 21. Step 8.

Step 9:

 Once the terminal block alignment bracket is in place, 

inspect it from the bottom to ensure that the teeth on the 

bracket separate each individual terminal block. Only one 

installed terminal block only should be visible between two 

teeth when the alignment bracket is properly positioned. 

Figure 22. Step 9.

Step 10:

 To remove already mounted terminal blocks, first 

remove the terminal block alignment bracket by performing 

Steps 2 and 3 in this section.

Step 11: 

Remove any terminal block by inserting a small 

screwdriver under the mounting plate retainment tab at the 

top front of the terminal block as shown, and gently pry 

down to release and remove the block from the mounting 

bracket. 

Step 11. 

Step 12: 

After all terminal blocks to be removed are 

removed, perform Steps 7, 8, and 9 in this section to com-

plete the removal process.

Summary of Contents for Power Defense PD-NF

Page 1: ...FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH BODILY INJURY OR PROPERTY DAMAGE WARNING THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS...

Page 2: ...rs secondary terminal blocks Figure 1 are mounted onto an insulated support frame on the top front portion of the drawout cassette Figure 1 Drawout Terminal Block For fixed mounted circuit breakers se...

Page 3: ...Step 3 Become familiar with the fixed terminal block mount ing plate where secondary connections are made Note N Secondary connection points have numerical and descriptive laser etched identifications...

Page 4: ...IMPORTANT KEEP IN MIND THAT THE SECONDARY TERMINAL BLOCKS ASSOCI ATED WITH DRAWOUT CIRCUIT BREAKERS ARE MOUNTED ON THE BREAKER S DRAWOUT CASSETTE FIGURE 11 ACCESSORY SECOND ARY PLUGS PLUG INTO A SECO...

Page 5: ...aker s secondary plug housing to ensure accurate terminal block placement In addition a terminal block alignment bracket is assembled to provide proper alignment and separation of each individual term...

Page 6: ...etween any mounted terminal blocks and put it aside for re installment after new terminal blocks are connected to the mounting bracket Figure 16 Step 3 Grasp Here Step 4 Connect the bottom part of the...

Page 7: ...Step 8 Step 9 Once the terminal block alignment bracket is in place inspect it from the bottom to ensure that the teeth on the bracket separate each individual terminal block Only one installed termin...

Page 8: ...tual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipm...

Reviews: