Sizing the Power-Sure 700
Instruction manual
IM1002004E September 2015 www.powerquality.eaton.com
Table 1. Eaton Power-Sure 700 ordering guidelines
T - k -
Options
A
Blank
= No options
B
= Bypass switch
2
M1
= Standard metering
(IQ 130)
M2
= Premium metering
(IQ 150)
S
= Surge
Nominal
input voltage
Delta input:
L, L, L, G
B
= 208
C
= 240
H
= 400
D
= 480
E
= 600
kVA ratings and dimensions
kVA
Weight
(lbs)
BTUs/
hr
Bypass
Metering
Cabinet size
Dimensions H x W x D in inches (mm)
010
010
015
015
025
030
045
050
075
100
125
150
225
300
500
440
520
520
600
870
890
950
1,176
1,575
2,014
2,137
2,240
3,300
4,000
5,500
1,025
1,205
1,540
1,540
2,560
3,090
4,600
7,332
9,514
11,833
14,748
17,698
23,000
30,750
51,250
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
30.20 x 22.20 x 29.00 (767.1 x 563.9 x 736.6)
44.20 x 22.20 x 29.00 (1122.7 x 563.9 x 736.6)
30.20 x 22.20 x 29.00 (767.1 x 563.9 x 736.6)
44.20 x 22.20 x 29.00 (1122.7 x 563.9 x 736.6)
44.20 x 22.20 x 29.00 (1122.7 x 563.9 x 736.6)
44.20 x 22.20 x 29.00 (1122.7 x 563.9 x 736.6)
44.30 x 45.90 x 29.00 (1125.2 x 1165.9 x 736.6)
66.00 x 29.00 x 35.50 (1676.4 x 736.6 x 901.7)
76.00 x 34.40 x 35.50 (1930.4 x 873.8 x 901.7)
76.00 x 34.40 x 35.50 (1930.4 x 873.8 x 901.7)
76.00 x 34.40 x 35.50 (1930.4 x 873.8 x 901.7)
76.00 x 34.40 x 35.50 (1930.4 x 873.8 x 901.7)
77.40 x 56.00 x 41.50 (1966.0 x 1422.4 x 1054.1)
77.40 x 56.00 x 41.50 (1966.0 x 1422.4 x 1054.1)
77.00 x 72.40 x 48.40 (1955.8 x 1839.0 x 1229.4)
Frequency
6
= 60 Hz
5
= 50 Hz
Nominal
output voltage
Wye output:
L, L, L, N, G
L
= 120/208
M
= 230/400
N
= 277/480
P
= 347/600
A
Units with no surge protection option, bypass option or metering will have blanks in the last three spaces in the catalog number.
B
Bypass is standard on 50 kVA and larger units and an option on 45 kVA and smaller units.
otess:
N
Listings—UL Listed, CSA Certified, except for 600 V: no UL, CSA on 600 V units.
For output distribution, call factory. K factor rated units available on request.
Sizing the Power-Sure 700
When sizing the Power-Sure 700, be sure to take into
consideration all loads and circuits the unit is to supply.
A good way to ensure that the Power-Sure 700 is sized
properly is to use the following guidelines:
●
●
List each piece of equipment, include model, voltage,
current, and kVA
●
●
Calculate kVA of load plus a safety margin
●
●
When this is not possible, gather the data by reading
the specification plate of the equipment you plan on
backing up
●
●
One method is to ask the vendor of the equipment to
supply you with the information you need
●
●
Be sure to verify the input supply voltage and the output
requirements of the Power-Sure 700
Installation considerations
Prior to installing the Power-Sure 700, be sure to take into
consideration the site you have selected. Power Conditioners
produce heat and therefore require ventilation, as well as
accessibility.
Consider these factors:
●
●
Ventilation
●
●
Size of the Power-Sure 700
●
●
Weight load
●
●
Audible noise requirements
●
●
Monitors
●
●
Options
●
●
Clean environment
●
●
Proper ground techniques
●
●
Input source voltage
●
●
Receiving facilities
●
●
Distribution of power
●
●
Room temperature
●
●
Clearances
●
●
Accessibility
●
●
Excessively long power runs