18
Installation
Instruction manual—single-phase power conditioners
IM01002005E September 2015 Eaton.com
2.4: Input volts and amps specifications 500 VA–5 kVA
Full kVA ratings may be used at 120 Vac on secondary windings (X1–N or X3–N) .
Table 2-1: Input volts and amps specifications 500 VA–5 kVA
Power rating
Model
120 V
208 V
240 V
480 V
500 VA
T800P-00500
4.6 A
2.6 A
2.3 A
1.1 A
750 VA
T800P-00750
6.9 A
3.9 A
3.4 A
1.7 A
1 kVA
T800P-01000
9.2 A
5.3 A
4.6 A
2.3 A
1.5 kVA
T800P-01500
13.7 A
7.9 A
6.8 A
3.4 A
2 kVA
T800P-02000
18.3 A
10.5 A
9.2 A
4.6 A
3 kVA
T800P-03000
27.5 A
15.8 A
13.7 A
6.9 A
5 kVA
T800
a
-05000
45.8 A
26.4 A
22.9 A
11.4 A
a
P = wall-mounted; F = floor-mounted .
Note:
Recommended input circuit breaker should be sized 125% of stated input amperage .
Input Output
●●
120V H1–H2
●●●●●
120V X1–N
●●
208V H1–H3
●●●●●
208V X1–X2
●●
240V H1–H4
●●●●●
240V X1–X3
●●
480V H1–H5
●●●●●
120V X3–N
Terminals
●●
#8 stud
●●●●●
#10 stud
●●
Maximum wire size:
10 AWG
●●●●●
Maximum wire size:
6 AWG
●●
Recommended torque:
15 lb in
●●●●●
Recommended torque:
20 lb in
Figure 2-9: Hardwiring for 500 VA–5 kVA units