Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
123
Figure 68. Typical System Status Screen
MAINTENANCE BYPASS
BYPASS
UPM: OFFLINE
SHUTDOWN
:
AVAILABLE
:
OFF
:
SYSTEM STATUS
CONTROL
S
ESC
F
F
O
R
E
G
R
A
H
C
:
UPS
Table 32. Typical System Status Messages
Function
Message
UPS
Shutdown; Bypass; Online; Online with ESS; VMMS; High Alert
Bypass
Off; On; Available
Maintenance Bypass
Off; On
Charger
Charger Off; Charging
UPM (during startup)
DC Starting, Charger Off; DC Starting, Close Battery Breaker; Inverter Starting;
Inverter Syncing; Ready; Online
UPM 1
UPM 4 (if FI-UPM is installed)
Offline; Shutdown, Charger Off; Ready; Ready, Charging; Online, Charger Off; Online,
Charging
Table 33. Command Menu Operation
Function
Subfunction
Operation
UPS Control
Commands
Use the up or down arrow pushbutton to highlight the command function
desired, then press the
SELECT
pushbutton to execute the command or
proceed to further command screens.
Go to Online
Starts the UPS in Online mode or transfers the UPS to Online mode from
Bypass mode.
Enable (Disable) Energy Saver
Enables or disables Energy Saver System mode. Enable changes to
Disable when the Energy Saver System mode is enabled.
Enable (Disable) Var Module
Management
Enables or disables the Variable Module Management System mode.
Enable changes to Disable when the Variable Module Management
System mode is enabled.
Start High Alert
Starts High Alert mode.
Go to Bypass
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from
Online mode.