124
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
Table 33. Command Menu Operation (Continued)
Function
Subfunction
Operation
Load Off
Displays the Load Off screen (see paragraph
Bypass
Commands
Use the up or down arrow pushbutton to highlight the command function
desired, then press the
SELECT
pushbutton to execute the command or
proceed to further command screens.
Go to Bypass
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from
Online mode.
Go to Online
Starts the UPS in Online mode or transfers the UPS to Online mode from
Bypass mode.
Enable (Disable) Energy Saver
Enables or disables Energy Saver System mode. Enable changes to
Disable when the Energy Saver System mode is enabled.
Enable (Disable) Var Module
Management
Enables or disables the Variable Module Management System mode.
Enable changes to Disable when the Variable Module Management
System mode is enabled.
Start High Alert
Starts High Alert mode.
Load Off
Displays the Load Off screen (see paragraph
Charger
Control
Commands
Use the up or down arrow pushbutton to highlight the command function
desired, then press the
SELECT
pushbutton to execute the command.
Charger On
Turns the battery charger on.
Charger Off
Turns the battery charger off.
UPM Control
Commands
Use the up or down arrow pushbutton to highlight the command function
desired, then press the
SELECT
pushbutton to execute the command.
UPM On
Turns the UPM on without transferring the load to Online mode. The Load
is on bypass.
UPM Off
Transfers the load to bypass and turns the UPM off.
UPM Go to Online
Turns the UPM on and transfers the load to Online mode.
Charger On
Turns the battery charger on.
Charger Off
Turns the battery charger off.
NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.
77..33
S
Siinnggllee U
UP
PS
S O
Oppeerraattiioonn
The paragraphs in this section provide operating instructions for a UPS system containing only one UPS.
NOTE
A Field Installed UPM (FI-UPM) is always designated as UPM 4.
77..33..11
S
Sttaarrttiinngg tthhee U
UP
PS
S iinn O
Onnlliinnee M
Mooddee
To start the UPS system: