UPS Operating Instructions
Power Xpert
TM
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716—Rev 8
www.eaton.com/powerquality
7-17
The
BYPASS
status indicator is illuminated. The Bypass status indicates
ON
. The UPM status indicates
SHUTDOWN, CLOSE BATTERY
.
7.3.9
Enable Energy Saver System Mode from the Bypass Command Menu
To enable Energy Saver System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select
ENABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates
ONLINE WITH ESS
. The UPM status
indicates
ONLINE
. If the battery is not charging, the power module is off.
7.3.10 Disable Energy Saver System Mode from the Bypass Command Menu
To disable Energy Saver System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select
DISABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Battery mode and then to Online mode.
The Online status indicator is illuminated. The UPS status indicates
ONLINE
. The UPM status indicates
ONLINE
.
NOTE
The Energy Saver System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled,
the Energy Saver System mode commands will not be displayed.
NOTE
The Energy Saver System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled,
the Energy Saver System mode commands will not be displayed.
Summary of Contents for Power Xpert 9395 550/275
Page 1: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Page 2: ......
Page 3: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Page 27: ...Section 1 Installation...
Page 28: ......
Page 207: ......
Page 208: ...164201716 8 164201716 8...