Product Specifications
10-2
Power Xpert
TM
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716—Rev 8
www.eaton.com/powerquality
10.2.2 UPS Output
10.2.3 UPS Environmental
UPS Output Capacity
100% rated current
Output Voltage Regulation
±
1% (10% to 100% load)
Output Voltage Adjustment
(N/
3%)
400 Vac nominal, adjustable from 388 Vac to 412 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
Output Voltage Harmonic Content
1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See Table 3-4 through Table 3-7.
Output Voltage Balance
3% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
3
for 100% maximum load imbalance (linear load)
Output Transients
±
5% (10% to 100% load)
Frequency Regulation
±
0.1 Hz free running
Synchronous to Bypass
+10% to -10%
±
3%
Frequency Slew Rate
1 Hz per second maximum
Load Compatibility
0.9 pF Leading
0.8 pF Lagging
Overload Capability
110% for 10 minutes
125% for 30 seconds
150% for 10 seconds
NOTE
The 110% overload capability in the above table is based on the kVA label rating of
the UPS. The 125% and 150% overloads are based on the non-derated hardware
capability of the UPS.
Operating Temperature
0 to 40
C (32 to 104
F) without derating. The recommended operating
temperature is 25
C (77
F).
Operating Altitude
Maximum 1000m (3000 ft) at 40
C without derating
Storage Temperature
–25 to +60
C, excluding batteries (prolonged storage above 40
C causes
rapid battery self
discharge)
Relative Humidity (Operating and
Storage)
5% to 95% maximum non-condensing
Acoustical Noise
76 dB at a 1m distance, A weighted
EMI Suppression
Meets FCC Regulation 47, Part 15, for class A devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without
damage and with no disturbance or adverse effect to the critical load.
Summary of Contents for Power Xpert 9395 550/275
Page 1: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Page 2: ......
Page 3: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Page 27: ...Section 1 Installation...
Page 28: ......
Page 207: ......
Page 208: ...164201716 8 164201716 8...