UPS Installation Plan and Unpacking
3-12
Power Xpert
TM
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual
164201716—Rev 8
www.eaton.com/powerquality
Table 3-7. Input/Output Ratings and External Wiring Requirements for the Power Xpert 9395-550/275 – 400V, Separate Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
225
205
225
250
450
410
500
455
550
500
Input and Output Voltage
Volts
400/400 400/400 400/400 400/400 400/400
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
370 453 741 823 905
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
300
(4)
300
(4)
300
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
325 397 650 722 794
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
350
(3)
350
(3)
350
(3)
350
(3)
350
(3)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
325 397 650 722 794
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
500
(3)
500
(3)
500
(3)
500
(3)
DC Input from Each Battery Cabinet to Each UPS UPM or Each Battery
Disconnect
(1) Positive, (1) Negative
C
Total
Amps
451 551 902 1002 1103
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(1)
500
(1)
500
(1)
500
(1)
500
(1)
DC Input from Each Battery Disconnect to Each UPS UPM
(1) Positive, (1) Negative
C
Total
Amps
451 551 902 1002 1103
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
250
(3)
250
(3)
250
(3)
250
(3)
250
(3)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
325 397 650 722 794
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
350
(3)
350
(3)
350
(3)
350
(3)
350
(3)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
325 397 650 722 794
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(3)
500
(3)
500
(3)
500
(3)
500
(3)
NOTE
V
Callout letters
A
,
B
,
C
, and
D
map to Figure 6-7. Callout letters
B
,
C
, and
D
NOTE
V
Because of the future upgradability to a fully rated 550 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 550 kVA.
Summary of Contents for Power Xpert 9395 550/275
Page 1: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Page 2: ......
Page 3: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Page 27: ...Section 1 Installation...
Page 28: ......
Page 207: ......
Page 208: ...164201716 8 164201716 8...