Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
113
C
Chhaapptteerr 77 U
UP
PS
S O
Oppeerraattiinngg IInnssttrruuccttiioonnss
This section describes how to operate the UPS using either the older LCD non-touch panel or the newer color
touchscreen control.
Refer to Section
or Section
Using the Color Touchscreen Control Panel
for
the appropriate item. This section describes how to operate the UPS.
NOTE 1
Before starting the UPS, ensure all installation tasks are complete and a preliminary
startup has been performed by authorized service personnel. The preliminary startup
verifies all electrical interconnections to ensure the installation was successful and the
system operates properly.
NOTE 2
Read this section of the manual and have thorough knowledge of UPS operation before
attempting to operate any of the controls.
NOTE 3
The UPS displays 2 minutes of battery runtime at the initial startup. After a 24-hour
charging period, the UPS automatically runs a battery test and the correct battery
runtime displays.
77..11
U
UP
PS
S C
Coonnttrroollss aanndd IInnddiiccaattoorrss
The controls and indicators identified and described in this section are used to control and monitor UPS
operation.
shows the controls and indicators.
Figure 63. UPS Controls and Indicators
Pushbutton
Control Panel
ISBM
UPM 1
AC Input Breaker CB1
(Optional)
(Not available with
separate rectifier feed
option.)