Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
11. On the System Status screen, select the
BYPASS
command.
12. Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
13. On the Bypass Control Command screen, select
GO TO BYPASS
.
14. Press the
SELECT
pushbutton on the Bypass Command menu bar.
The critical load is immediately supplied by the bypass source in Bypass mode from all UPSs.
The
BYPASS
status indicator is illuminated. The Bypass status indicates
ON
. The UPM status indicates
SHUTDOWN, CLOSE BATTERY
.
77..44..99
EEnnaabbllee EEnneerrggyy S
Saavveerr S
Syysstteem
m M
Mooddee ffrroom
m tthhee B
Byyppaassss C
Coom
mm
maanndd M
Meennuu
To enable Energy Saver System mode:
NOTE 1
The Energy Saver System mode commands are displayed only if enabled at the factory
or by an Eaton Customer Service Engineer.
NOTE 2
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the BYPASS command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select
ENABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates
ONLINE WITH ESS
. The UPM status
indicates
ONLINE
. If the battery is not charging, the power module is off.
77..44..1100 D
Diissaabbllee EEnneerrggyy S
Saavveerr S
Syysstteem
m M
Mooddee ffrroom
m tthhee B
Byyppaassss C
Coom
mm
maanndd M
Meennuu
To disable Energy Saver System mode:
NOTE 1
The Energy Saver System mode commands are displayed only if enabled at the factory
or by an Eaton Customer Service Engineer.
NOTE 2
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled, the
Energy Saver System mode commands will not be displayed.
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
. On the Bypass Control Command screen, select
DISABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Battery mode and then to Online mode.