Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
197
C
Chhaapptteerr 1100 P
Prroodduucctt S
Sppeecciiffiiccaattiioonnss
1100..11
M
Mooddeell N
Nuum
mbbeerrss
The UPS is housed in a free-standing cabinet with safety shields behind the door and front panels. The UPS is
available in 50 or 60 Hz with various output power ratings.
Models
Power Rating
Frequency
Power Xpert 9395-550/225
225 kVA
50/60 Hz
Power Xpert 9395-550/275
275 kVA
50/60 Hz
Power Xpert 9395-550/450
450 kVA
50/60 Hz
Power Xpert 9395-550/500
500 kVA
50/60 Hz
Power Xpert 9395-550/550
550 kVA
50/60 Hz
1100..22
S
Sppeecciiffiiccaattiioonnss
The following sections detail the input, output, battery, and environmental specifications for the UPS.
1100..22..11 U
UP
PS
S IInnppuutt
Operating Input Voltage
400 Vac
480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See
through
.
Reduced for Generator
Adjustable
Input Current Harmonic Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
Battery Voltage
480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A
Battery Shunt Trip