Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
17
•
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
•
The cabinet can be installed in
line-up-and-match
or
standalone
configurations.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in
and the size
requirements shown in
through
. Dimensions are in millimeters (inches).
For Field Installed UPM (FI-UPM) weights and dimensions, refer to the
Eaton 9395 Field Installed UPM
Mechanical Installation Manual
, listed in paragraph
Includes the weights of the heaviest cabinet configuration. Actual weights may be less due to installed
configuration. Weights are in kilograms (pounds).
Table 2. UPS Cabinet Maximum Weights
Model
Maximum Weight kg (lb)
Shipping
Installed
Power Xpert 9395-550/275
930 (2050)
903 (1990)
The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in
. Dimensions are in
millimeters (inches).
Table 3. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18") minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36") working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
•
Ambient Temperature Range: 0–40º C (32–104º F)
•
Recommended Operating Range: 20–25º C (68–77º F)
•
Maximum Relative Humidity: 95%, non-condensing
If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental
requirements supercede the UPS requirements. Operating temperatures above the recommended range will
result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to
Eaton’s
Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book
for
more information. These documents can be found at www.eaton.com/ powerquality or contact an Eaton
service representative to obtain copies.
The UPS ventilation requirements are shown in