64
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
Figure 27. Typical Battery Interface Connection — Common Battery System
Battery
Breaker or
Disconnect
TB1
Battery Aux
Battery Aux Common
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
UPS
ST
5
6
7
8
NOTE
Battery Aux and DC Shunt Trip wiring should be a minimum of 18 AWG.
Figure 28. Typical Battery Interface Connection – Separate Battery System
UPM 1
Battery
Breaker or
Disconnect
TB1
UPS
ST
UPM 4
Battery
Breaker or
Disconnect
ST
48 Vdc
Battery Aux
Battery Aux Return
5
6
7
8
NOTE
Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
44..77..33
X
X--S
Slloott C
Coonnnneeccttiioonnss
NOTE
LAN and telephone drops for use with X-Slot cards must be provided by the customer.
NOTE
When installing external wiring to X-Slot cards, conduit must be installed to the UPS
cabinet. When installing internal wiring to X-Slot terminals, route the wiring through the
internal opening in the X-Slot communication bay.
NOTE
For installation and setup of an X-Slot card, contact an Eaton service representative (see