26
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
Table 6. Input/Output Ratings and External Wiring Requirements for the Power Xpert 9395-550/275 – 400V, Common
Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
225
205
275
250
450
409
500
455
550
500
Input and Output Voltage
Volts
400/400
400/400
400/400
400/400
400/400
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
370
453
741
823
905
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
300
(4)
300
(4)
300
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
325
397
650
722
794
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
350
(3)
350
(3)
350
(3)
350
(3)
350
(3)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
325
397
650
722
794
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
500
(3)
500
(3)
500
(3)
500
(3)
DC Input from Each Battery Cabinet to UPS or
Battery Disconnect
(1) Positive, (1) Negative
C
Total Amps
451
551
902
1002
1103
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(1)
500
(1)
500
(1)
500
(1)
500
(1)
DC Input from Each Battery Disconnect to Each
UPS UPM
(1) Positive, (1) Negative
C
Total Amps
451
551
902
1002
1103
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
350
(6)
350
(6)
350
(6)
350
(6)
350
(6)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
325
397
650
722
794
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
350
(3)
350
(3)
350
(3)
350
(3)
350
(3)