shows the wiring connections if the normally-closed REPO contacts are used and
shows
alternative methods of connecting a REPO switch if using another manufacturer's switch.
Figure 53. Normally Closed REPO Switch Wiring
3 (NO )
REPO
Switc h
(NC)
Twiste d
Wires
1 (NC)
1
2
NOTE
REPO switch rating is 24 Vdc, 1A minimum.
NOTE
The REPO switch must be a latching-type switch not tied to any other circuits.
NOTE
REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common.
UPS TB1
2 (Return)
4 (Return)
Figure 54. Normally Closed and Normally Open REPO Switch Wiring
3 (NO )
1 (NC)
UPS TB1
2 (Return)
4 (Return)
REPO
(NO )
Twisted
Wires
REPO
Switch
(NC)
Switch
NOTE
REPO switch rating is 24 Vdc, 1A minimum.
NOTE
The REPO switch must be a latching-type switch not tied to any other circuits.
NOTE
REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common.