Eaton
®
Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
191
NOTE
Depending on the system configuration, the last online UPM in a system may not shut
down or the UPS may transfer to BP.
1.
Make sure you are logged in for user access (see
).
2.
Press the
Controls
button on the
Home
screen (see
). The
System Status
screen is displayed
(see
3.
Select
Module Controls
. The Module Controls screen is displayed (see
).
4.
On the Module Controls screen, select the applicable UPM details button. The UPM
Module Controls
Detail
screen appears (see
5.
On the UPM Module Control Detail screen, select
Shutdown UPM
. Select
Yes
on the confirmation
screen.
6.
Verify the following:
UPM "x" IS SHUTTING DOWN
message appears
The UPM POWER STATUS shows
Idle
on the
Module Control Detail
screen, (see
The UPM status bar shows in a gray color (Idle).
NOTE
The shutdown UPM button must be pressed twice to fully shutdown the UPM.
7.
Repeat step 4.
8.
Verify the following:
UPM "x" IS SHUTTING DOWN
message appears
The UPM POWER STATUS shows
Shutdown
on the Module Control Detail screen, (see
).
The UPM status bar shows in a black color (Shutdown)
The UPM rectifier and inverter turn off.
Logic power remains on.
9.
Repeat the procedures in this section to shut down any other UPMs as applicable.
77..44..1155 S
Siinnggllee U
UP
PM
M R
Reessttaarrtt
To restart a single UPM from a shutdown state refer to the procedures in
Starting a Single UPM to Online Mode
77..44..1166 C
Chhaarrggeerr C
Coonnttrrooll
To turn the battery charger on:
1.
Make sure you are logged in for user access (see
).
2.
Press the
Controls
button on the
Home
screen (see
). The
System Status
screen is displayed
(see
3.
On the System Status screen, select
Module Controls
. The Module Controls screen is displayed (see
4.
Select the Module Controls Detail screen for the applicable UPM to start the charger (see
5.
Select
Start Charger
. The charger status shows
Charger On
.
To turn the battery charger off:
1.
Make sure you are logged in for user access (see
).