218
Eaton
®
Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
•
When replacing batteries, use the same number of sealed, lead–acid batteries.
•
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
•
Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
•
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
99..22
P
Peerrffoorrm
miinngg P
Prreevveennttiivvee M
Maaiinntteennaannccee
The UPS system requires very little preventive maintenance. However, the system should be inspected
periodically to verify that the units are operating normally and that the batteries are in good condition.
99..22..11
D
DA
AIILLYY M
Maaiinntteennaannccee
Perform the following steps daily:
1.
Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the
unit.
2.
Ensure the air intakes (vents on the front door and panel) and the exhaust opening (on top of the UPS
cabinet) are not blocked.
3.
Ensure the operating environment is within the parameters specified in paragraph
Environmental and Installation Considerations
and
.
4.
Ensure the UPS is in Online mode (Online status indicator is illuminated). If an alarm lamp is illuminated or
the Online status indicator is not illuminated, contact an Eaton service representative.
99..22..22
M
MO
ON
NTTH
HLLYY M
Maaiinntteennaannccee
Perform the following steps monthly:
1.
Monitor system parameters as described in paragraph
Using the Color Touchscreen Control Panel
2.
Check the UPS air filters (located behind the front panels or door) and wash or replace as necessary. See
and
for filter locations, and
for filter sizes. Contact an Eaton service
representative for replacement filters. To remove the filters:
Table 45. UPS Filter Sizes
Filter Location
Size
Bottom Left ISBM Section Air Filters (Continuous Static Switch only)
12" x 20" x 0.25"
Bottom Right ISBM Section Air Filters (Continuous Static Switch only)
12" x 20" x 0.25"
Middle Right ISBM Section Air Filter (Continuous Static Switch only)
20" x 6.3" x 0.25"
FI-UPM Section Air Filters
20" x 44" x 0.25"
Verify washed filters are thoroughly dry before reinstalling.
ATTENTION!
Vérifier que les filtres sont bien secs avant de les réinstaller.
a.
Remove one top screw and two bottom screws securing each UPM front panel (see
). Lift
each panel straight up to remove it from the panel hanger bracket at the top of the cabinet.