Table 26. Recommended Input Circuit Breaker Ratings (100% and 80% Load Rating) (Continued)
UPS Model
Input Rating
%
480V
415V
400V
380V
Eaton 9395P-900/675
100
2000A
2000A
2000A
2000A
80
1600A
1600A
1600A
1600A
Eaton 9395P-900/600
100
1000A
1200A
1200A
1200A
80
1200A
1600A
1600A
1600A
Eaton 9395P-900/550
100
1000A
1000A
1000A
1000A
80
1200A
1200A
1200A
1200A
Eaton 9395P-900/500
100
800A
1000A
1000A
1000A
80
1000A
1200A
1200A
1200A
Eaton 9395P-900/450
100
700A
800A
800A
800A
80
1000A
1000A
1000A
1000A
Eaton 9395P-900/400
100
600A
700A
800A
800A
80
800A
1000A
1000A
1000A
NOTE Because of the future upgradability to a fully rated 900 kW UPS with the addition of the FI-UPM, Eaton recommends
using the breaker size specified for a 1100 kW UPS.
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings
from
in accordance with the NEC, ANSI/NFPA 70.
ATTENTION!
Pour réduire le risque d’incendie, ne brancher qu’à un circuit avec le courant nominal maximal du disjoncteur
d’entrée indique dans le tableau (
) conformement à la norme ANSI/ NFPA 70 du NEC.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in
to
. The recommended line-to-line load unbalance is 50%
or less.
Bypass and output overcurrent protection and bypass and output disconnect switches are to be provided by
the customer. Module Output Breakers (MOBs) are to be provided by the customer.
lists the recommended rating for 480V, 415V, 400V, and 380V bypass, output, and MOB circuit
breakers. Bypass breakers are not applicable for IOM configurations.
NOTE
For the 9395P-900 400/415/380V models, the max output is 825 kW/ 825 kVA.