94
Eaton
®
Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
Figure 47. Terminal Blocks TB1, TB2, and TB3 Connector Assignments
TB1
TB2
Alarm Relay NC
Alarm Relay Com m on
Alarm Relay NO
REPO NO
REPO NC
REPO Return
Battery Aux
Battery Aux Com m on
Battery Shunt Trip +
+Battery Shunt Trip –
Alarm Relay Com m on
Pull Chain
Pull Chain Com m on
REPO Return
UPS
1
10
TB3
1
10
1
10
UPS
NOTE All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either
normally-open or normally-closed contacts. All control wiring and relay and switch contacts are customer-supplied.
NOTE The building alarms can be programmed to display the alarm functional name.
NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used.
Output Contactor K3 NC Aux Common
Output Contactor K3 NC Aux
Building Alarm 1
Building Alarm Return 1
Building Alarm 2
Building Alarm Return 2
Building Alarm 3
Building Alarm Return 3
Building Alarm 4
Building Alarm Return 4
Building Alarm 5
Building Alarm Return 5