Eaton
®
Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
107
Figure 56. Hot Sync CAN Bridge Card Connections
Connections for Parallel System Control
Connections for RMP II, RIM II, or SCM II
Alarm
J3
Connections for Bypass Status
Table 32. Hot Sync CAN Bridge Card Interface Connections
J3 Terminal
Name
Description
1
Alarm
Programmable UPS alarm. Activated by a remote dry contact closure.
2
Alarm Return
3
Alarm Relay NC
Normally closed contact opens when UPS is on bypass.
4
Alarm Relay Com
Bypass contact return.
5
Alarm Relay NO
Normally open contact closes when UPS is on bypass.
6
TX
RMP II, RIM II, and SCM II connections.
7
TX
8
CAN L
CAN Input for parallel operation.
9
Can H
10
Shield