background image

172

Eaton

®

Power Xpert

®

9395P-900 Installation and Operation Manual 164000501—Rev 12

77..33..1100 S

Syysstteem

m EEvveennttss M

Maaiinn S

Sccrreeeenn

When the UPS system is running in Online mode, it continually monitors itself and the incoming utility power.
In Battery or Bypass modes, the UPS may issue alarms to display exactly what event caused the change from
Online mode. System events on the UPS can be indicated by horns, lights, messages, or all three. The System
Events screen can be accessed from the Home screen with the

LOGS

button. See

Figure 113

.

Figure 113. System Events Screen

77..33..1111 U

Usseerr LLoogg

Select

LOGS

from the menu bar on the main menu screen to look at the active events screen. This screen

shows any currently active alarms, notices, or commands.

System Event Horns

– The system event horn beeps to alert an operator that an event needing attention

is taking place. The horn cycles at a half-second rate.

System Event Indicators

– The status indicators on the UPS control panel work with the event horn to let

the operator know when the UPS is operating in any mode other than normal. Only the ON indicator is
visible during normal UPS system operation. The other indicators illuminate to indicate alarms or events.
When an alarm occurs, first check these indicators to see what type of event has taken place. For
descriptions of the status indicators, see paragraph

7.3.1

Status Indicators

.

System Event Messages

– When a system event occurs, a message appears on the LCD in the UPS

status area. This message is also written to the Active Events Log and may be added to the History Log.
The messages are divided into four categories: alarms, notices, status, and commands.

The user log window (

1

) allows the operator to enter any number up to the number shown to the right of the

box. Each window shows five events. The operator can also use the UP/DOWN arrows above and below the
blue field (

2

) showing the number of events in the log. See

Figure 114

.

UPS Operating Instructions

Summary of Contents for Power Xpert 9395 High Performance

Page 1: ...0501 Revision 12 900 kW 900 kVA Installation and Operation Manual For use with Two UPM 450 600 kVA Three UPM 675 900 kVA and Plus 1 675 900 kVA UPS Models Eaton Power Xpert 9395 High Performance 9395P...

Page 2: ...INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS Please read all instructions before operating the equipment and save this...

Page 3: ...m a host of threats including power outages surges lighting strikes and enable you to monitor and control your power infrastructure We trust that your Eaton 9395 Uninterruptible Power Supply system wi...

Page 4: ...e license to use the Firmware in conjunction with the operation of the product to which the Firmware pertains or other products as described by Eaton in the Documentation Licensee does not acquire any...

Page 5: ...CT IS AT LICENSEE S SOLE RISK 5 0 GENERAL PROVISIONS 5 1 Update Policy Eaton may from time to time but has no obligation to create Updates of the Firmware or components thereof 5 2 Limitation on Liabi...

Page 6: ...nctions Programs Pages Programs aspx or to any national of any such country wherever located who intends to transmit or transport the Firmware back to such country ii to any end user who Licensee know...

Page 7: ...nfidential aspects of the Firmware shall not be disclosed to third parties without the prior written consent of Eaton Accordingly Eaton will be entitled to preliminary and permanent injunctive and oth...

Page 8: ......

Page 9: ...System 7 1 3 6 Input Output Module Configuration 7 1 3 7 Continuous Static Switch 7 1 3 8 Inherent Redundancy 8 1 3 9 Energy Saver and High Alert Modes 8 1 3 10 Variable Module Management System and H...

Page 10: ...attery Interface Connections 95 4 9 3 X Slot Connections 96 4 10 Installing a REPO Switch 97 4 11 Installing Options Accessories and Distributed Bypass Control Wiring 101 4 12 Initial Startup 101 4 13...

Page 11: ...mation Pop Up 165 7 3 7 Meters Summary Screen 165 7 3 8 Input Bypass and Output Meters Screens 166 7 3 9 Battery Meters Screen 171 7 3 10 System Events Main Screen 172 7 3 11 User Log 172 7 3 12 Batte...

Page 12: ...ode 197 7 5 7 Start Variable Module Management System High Alert Mode 197 7 5 8 Starting the Distributed Bypass System in Bypass Mode 197 7 5 9 Starting the UPS UPMs 198 7 5 10 Starting a Single UPM 1...

Page 13: ...aintenance 218 9 2 1 DAILY Maintenance 218 9 2 2 MONTHLY Maintenance 218 9 2 3 PERIODIC Maintenance 221 9 2 4 ANNUAL Maintenance 221 9 2 5 BATTERY Maintenance 221 9 3 Installing Batteries 222 9 4 Recy...

Page 14: ...xiv Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Table of Contents...

Page 15: ...Center of Gravity FI UPM and 2X UPMs 32 Figure 19 UPS Center of Gravity 3X UPMs 33 Figure 20 UPS Center of Gravity 2X UPMs 34 Figure 21 Remote EPO Switch Dimensions 35 Figure 22 UPS Cabinet as Shipped...

Page 16: ...l Chain Wiring with MOBs 111 Figure 60 Remote Monitor Panel II and Remote Monitor Panel II Terminal Locations 113 Figure 61 Remote Monitor Panel II Relay Interface Module II or Supervisory Contact Mod...

Page 17: ...0 Configurations 151 Figure 89 Typical Distributed Bypass System 2 1 and 3 0 Configurations 152 Figure 90 Typical Distributed Bypass System 3 1 and 4 0 Configurations 153 Figure 91 UPS Controls and In...

Page 18: ...179 Figure 126 Disable ESS Screen 180 Figure 127 High Alert Timer Screen 180 Figure 128 Statistics Basic Screen 181 Figure 129 Statistics Data Detail Screen 181 Figure 130 ESS Comparison Screen 182 F...

Page 19: ...e Battery 42 Table 14 400V Input Output Ratings and External Wiring Requirements for the Three Four UPM Models Common Battery 43 Table 15 400V Input Output Ratings and External Wiring Requirements for...

Page 20: ...ble 36 RMP II RIM II or SCM II Wiring Terminations 114 Table 37 J1 through J4 Interface Connectors 116 Table 38 Oneline Configurations 130 Table 39 Status Indicators 158 Table 40 Security Levels and F...

Page 21: ...ularities that are inherent in commercial utility power Working with a building s electrical system the UPS system supplies clean consistent power that sensitive electronic equipment requires for reli...

Page 22: ...S The Power Xpert 9395P 900 Two UPM UPS 450 600 kVA contains two sections see Figure 1 an ISBM or an IOM section rated for a maximum of 900 kVA to provide future upgradability a UPM section containin...

Page 23: ...to provide future upgradability a UPM section containing two UPMs each UPM rated for a maximum of 300 kVA for a total maximum of 600 kVA an FI UPM section to provide N 1 redundancy for the system if t...

Page 24: ...hree UPM UPS model 675 900 kVA contains two sections see Figure 3 an ISBM or an IOM section rated for a maximum of 1200 kVA to provide future upgradability a UPM section containing three UPMs Each UPM...

Page 25: ...of 300 kVA for a total maximum of 900 kVA an FI UPM section which provides N 1 redundancy for the system see paragraph 1 3 2 Field Installed UPM Figure 4 Eaton Xpert 9395P 900 Three UPM Plus 1 FI UPM...

Page 26: ...information X Slot Communication Bays Four communication bays are standard equipment One to four optional X Slot connectivity cards can be installed in the UPS module at any time X Slot cards are quic...

Page 27: ...st tr riib bu ut te ed d B By yp pa as ss s S Sy ys st te em m There are two types of redundancy UPS based based on the number of UPSs and UPM based based on the number of UPMs NOTE All UPSs in the di...

Page 28: ...to double conversion mode or if in double conversion mode remains in double conversion mode for a default time period of one hour High Alert mode allows the user to place the unit in double conversio...

Page 29: ...spatch of technicians PredictPulse requires a Power Xpert Gateway Card PXGX connectivity card in an X Slot communication bay and an Environmental Monitoring Probe EMP for battery temperature humidity...

Page 30: ...TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as important operating and maintenance instructions This symbol indicates that you should not discard the UPS or t...

Page 31: ...optional features procedures for using with the UPS and information about maintenance Refer to the Eaton 9395P Field Installed UPM Mechanical Installation Manual P 164000503 for the following addition...

Page 32: ...12 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Introduction...

Page 33: ...carry live voltage even when the UPS is disconnected from an AC source To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environment free of...

Page 34: ...onnement du produit Lors de la v rification du fonctionnement de l UPS ne pas enlever la mise la terre si des charges y sont raccord es Ne pas ouvrir ni ab mer les batteries L lectrolyte qu elles cont...

Page 35: ...r les portes de l onduleur ferm es et les panneaux avant en place pour garantir une circulation ad quate de l air de refroidissement et pour prot ger le personnel des tensions dangereuses dans l unit...

Page 36: ...ompl tement les fourches dans les passages de fourche de la base NE PAS ins rer partiellement les fourches dans les passages pour d placer l armoire Il est possible d ins rer partiellement les fourche...

Page 37: ...nd Chapter 4 UPS System Installation to create a logical plan for installing the system 3 3 2 2 P Pr re ep pa ar riin ng g t th he e S Siit te e For the UPS system to operate at peak efficiency the in...

Page 38: ...sues One is the creation of microclimates which are persistent variations of temperature and or RH within a single room for example one side of the room is always cooler than the other side no matter...

Page 39: ...9395P 900 900 Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 ISBM CSS 808 1782 764 1684 3XUPM 496 1094 475 1047 FI UPM 496 1094 764 1684 Eaton 9395P 900 600 Eaton 9395...

Page 40: ...e same room as the UPS the battery cabinet environmental requirements supercede the UPS requirements Operating temperatures above the recommended range will result in decreased battery life and perfor...

Page 41: ...2 18 2 Eaton 9395P 900 550 CSS 550 kVA 550 kVA 480 480 72 2 18 2 Eaton 9395P 900 500 CSS 500 kVA 500 kVA 480 480 63 8 16 1 Eaton 9395P 900 450 CSS 450 kVA 450 kVA 480 480 54 1 13 6 NOTE CSS Continuou...

Page 42: ...41 7 7 Eaton 9395P 900 450 CSS 450 kVA 450 kVA 400 400 63 3 15 9 NOTE CSS Continuous Static Switch IOM Input Output Module Table 7 380V Air Conditioning and Ventilation Requirements During Full Load O...

Page 43: ...n Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 23 Figure 5 UPS Cabinet Dimensions Three UPM Front View Dimensions are in millimeters inches UPS Installation Plan and Unpack...

Page 44: ...Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 6 UPS Cabinet Dimensions Two UPM Front View Dimensions are in millimeters inches 1880 74 0 3036 9 119 5 UPS Installation Plan...

Page 45: ...pert 9395P 900 Installation and Operation Manual 164000501 Rev 12 25 Figure 7 UPS Cabinet Dimensions Right Side View Dimensions are in millimeters inches 892 35 40 1 6 830 32 7 UPS Installation Plan a...

Page 46: ...ev 12 Figure 8 ISBM Section Dimensions Front View Dimensions are in millimeters inches 1880 74 0 1705 67 1 For 4 wire systems only Figure 9 ISBM Section Dimensions Top View Front Dimensions are in mil...

Page 47: ...l 164000501 Rev 12 27 Figure 10 ISBM Section Dimensions Bottom View Front Dimensions are in millimeters inches Figure 11 UPM Section Dimensions Three UPM Front View Dimensions are in millimeters inche...

Page 48: ...al 164000501 Rev 12 Figure 12 UPM Section Dimensions Three UPM Top View Front Dimensions are in millimeters inches Figure 13 UPM Section Dimensions Two UPM Front View Dimensions are in millimeters inc...

Page 49: ...Installation and Operation Manual 164000501 Rev 12 29 Figure 14 UPM Section Dimensions Two UPM Top View Front Dimensions are in millimeters inches 1015 43 40 0 34 44 1 4 37 14 1 5 758 83 29 9 UPS Inst...

Page 50: ...501 Rev 12 Figure 15 UPM Section Dimensions FI UPM Front View Dimensions are in millimeters inches 1880 74 0 735 9 29 0 Figure 16 UPM Section Dimensions FI UPM Top View Front Dimensions are in millime...

Page 51: ...ty FI UPM and 3X UPMs 1880 74 0 DIMENSIONS MM IN CENTER OF GRAVITY THREE UPMS 361 14 3 362 14 3 357 14 1 900 35 4 918 36 1 850 33 5 362 14 3 918 36 1 900 1 kVA UPS FI UPM ISBM IOM 3XUPM A B A B Side V...

Page 52: ...ity FI UPM and 2X UPMs DIMENSIONS MM IN CENTER OF GRAVITY THREE UPMS 361 14 3 362 14 3 357 14 1 900 35 4 918 36 1 850 33 5 362 14 3 918 36 1 900 1 kVA UPS FI UPM ISBM IOM 2XUPM A B 759 29 9 2119 83 4...

Page 53: ...3 Figure 19 UPS Center of Gravity 3X UPMs DIMENSIONS MM IN CENTER OF GRAVITY THREE UPMS 360 14 3 357 14 1 896 35 3 850 33 5 362 14 3 918 36 1 900 kVA UPS ISBM 3XUPM A B 2172 85 5 983 38 7 1029 40 5 Si...

Page 54: ...12 Figure 20 UPS Center of Gravity 2X UPMs DIMENSIONS MM IN CENTER OF GRAVITY TWO UPMS 360 14 3 357 14 1 896 35 3 850 33 5 362 14 3 918 36 1 900 1 kVA UPS ISBM 2XUPM A B 759 29 9 1850 72 8 A ISBM 2XUP...

Page 55: ...fication is for copper wire with a 75 C rating Material and labor for external wiring requirements are to be provided by designated personnel If installing a maintenance bypass a minimum of two separa...

Page 56: ...ted in Table 24 Select overcurrent protection input battery and output breakers according to the UPS nameplate rated for either 80 or 100 Follow all applicable NEC and local codes For three or four UP...

Page 57: ...ions Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time Battery Cable Routing Require...

Page 58: ...each 500 3 500 3 500 3 500 3 500 3 AC Output to Critical Load Full Load Current 3 Phases 1 Ground D Amps 812 902 992 1083 1083 Minimum Conductor Size Number per Pole AWG or kcmil each 500 3 500 3 500...

Page 59: ...attery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time Battery Cable Routing Requirements...

Page 60: ...500 3 500 3 500 3 500 3 500 3 AC Output to Critical Load Full Load Current 3 Phases 1 Ground D Amps 541 601 662 722 722 Minimum Conductor Size Number per Pole AWG or kcmil each 500 4 500 4 500 4 500 4...

Page 61: ...rs A C and D map to Figure 82 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity show...

Page 62: ...1 Positive 1 Negative AWG or kcmil each 500 3 500 3 500 3 500 3 500 3 500 3 500 3 AC Output to Critical Load Five Wire Full Load Current 3 Phases 1 Neutral 1 Ground D Total Amps 626 696 765 835 939 10...

Page 63: ...rs A C and D map to Figure 82 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity show...

Page 64: ...1 Positive 1 Negative AWG or kcmil each 500 3 500 3 500 3 500 3 500 3 500 3 500 3 AC Output to Critical Load Five Wire Full Load Current 3 Phases 1 Neutral 1 Ground D Total Amps 650 722 794 866 974 10...

Page 65: ...tters A C and D map to Figure 82 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity s...

Page 66: ...00 4 500 4 500 5 500 6 500 6 500 6 NOTE Callout letters A B C and D map to Figure 72 NOTE If a 4 pole Automatic Transfer Switch ATS is used to connect the UPS to a generator or alternative input sourc...

Page 67: ...UPM 2 E3A UPM 3 E3A UPM 4 Four UPM Model Phase C 4 stud mounting 14 2 10 4 M8 AC Output from UPM Section E9A UPM 1 E9A UPM 2 E9A UPM 3 E9A UPM 4 Phase A 4 stud mounting 14 2 10 4 M8 E10A UPM 1 E10A U...

Page 68: ...Phase A 6 2 bolt mounting 76 56 M12 E2 Phase B 6 2 bolt mounting 76 56 M12 E3 Phase C 6 2 bolt mounting 76 56 M12 AC Input to Bypass E6 Phase A 6 2 bolt mounting 76 56 M12 E7 Phase B 6 2 bolt mountin...

Page 69: ...ery Input Output and Ground 180500037 120 Nut M12 86 Rectifier Input Bypass Input Battery Input Output and Ground 180200001 07 NOTE Bypass terminations are not applicable to IOM configurations Table 2...

Page 70: ...put to Bypass and Output A B C Ground 4 3 4 DC Common Battery Battery Positive Negative Ground 5 3 5 3 All models DC Separate Battery per UPM Battery Positive Negative Ground 7 4 1 NOTE 1 Because of t...

Page 71: ...9395P 900 550 Eaton 9395P 900 500 415 Vac AC Input to UPS Rectifier A B C Ground 5 3 5 AC Input to Bypass and Output A B C Ground 4 3 4 DC Common Battery Battery Positive Negative Ground 6 3 6 Eaton...

Page 72: ...Battery Battery Positive Negative Ground 8 3 5 4 Eaton 9395P 900 675 400 Vac 380 Vac AC Input to UPS Rectifier A B C Ground 6 3 6 AC Input to Bypass and Output A B C Ground 6 3 6 DC Common Battery Bat...

Page 73: ...cable to IOM configurations Battery Conductor Routing Refer to the notes at the bottom of Table 8 to Table 17 Input Output Ratings and External Wiring Requirements External overcurrent protection and...

Page 74: ...of fire connect only to a circuit provided with maximum input circuit breaker current ratings from Table 26 in accordance with the NEC ANSI NFPA 70 ATTENTION Pour r duire le risque d incendie ne branc...

Page 75: ...ure upgradability to a fully rated 900 kW UPS with the addition of the FI UPM Eaton recommends using the breaker size specified for a 1100 kW UPS There is no manual DC disconnect device within the UPS...

Page 76: ...5P 900 900 Eaton 9395P 900 600 800A Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 Eaton 9395P 900 600 Eaton 9395P 900 550 Eaton 9395P 900 500 Eaton 9395P 900 450 700A...

Page 77: ...attery Aux and 48 Vdc Shunt Trip signal wiring from the UPS must be connected to the DC source disconnect device Battery Aux and 48 Vdc Shunt Trip wiring should be a minimum of 18 AWG The REPO feature...

Page 78: ...tor The output of this UPS will not directly support phase to neutral loads MOBs with dual auxiliary contacts are to be provided by the customer Table 27 lists the recommended rating for the MOBs The...

Page 79: ...n position horizontale avant de les ins rer dans les passages de fourche NE PAS orienter les pointes de fourche vers le haut Ins rer compl tement les fourches dans les passages de fourche de la base N...

Page 80: ...elles pourraient se renverser 3 Set the pallet on a firm level surface allowing a minimum clearance of 3m 10 ft on each side for removing the cabinet from the pallet NOTE The ISBM and UPM sections are...

Page 81: ...Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 61 Figure 22 UPS Cabinet as Shipped on Pallet ISBM Section For 4 wiring systems only UPS Installation Plan and Unpacking...

Page 82: ...62 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 23 UPS Cabinet as Shipped on Pallet UPM Section UPS Installation Plan and Unpacking...

Page 83: ...the conduit landing plates to add conduit landing holes as required Plate material is 16 gauge steel 1 5 mm 0 06 thick If perforated floor tiles are required for ventilation place them in front of the...

Page 84: ...a section de l onduleur lorsque l armoire est soulev e ou d plac e Soulever ou d placer la section de l onduleur en n utilisant que les passages de fourche l avant ou l arri re V rifier que les fourch...

Page 85: ...at the beginning of this procedure 2 Remove the three bolts securing the left side shipping bracket to the cabinet and three bolts securing the bracket to the pallet see Figure 24 or Figure 26 Remove...

Page 86: ...g a forklift see the caution statement at the beginning of this procedure raise the UPS cabinet section until the cabinet bottom clears the pallet by approximately 3 mm 1 8 5 Pull the pallet from unde...

Page 87: ...Operation Manual 164000501 Rev 12 67 Figure 26 Removing the UPM Section Left Side Shipping Bracket Shipping Bracket Bolts Shipping Bracket Bolts Pallet Left Side Shipping Bracket UPM Removable Front...

Page 88: ...ted space to slide the sections together from the sides NOTE 2 For the following steps verify that the forklift or pallet jack is rated to handle the weight of the section see Table 2 for cabinet weig...

Page 89: ...ft Side Panel Wireway Panel UPM Section 5 Remove the screws securing the left top panel and remove the panel see Figure 28 Retain the hardware for later use 6 Remove the screws securing the left middl...

Page 90: ...nt of the cabinet bases are flush with each other see Figure 29 8 Reinstall the corner channel see Figure 28 and secure using the retained hardware 9 Reinstall the left middle panel see Figure 28 and...

Page 91: ...View Base Bracket UPM Section Base ISBM Section Base Bracket from Kit Screw from Kit Screw from Kit 4 4 4 4 E Elle ec ct tr riic ca alllly y C Co on nn ne ec ct tiin ng g t th he e S Se ec ct tiio on...

Page 92: ...Preparation for wiring and termination requirements NOTE AC output intercabinet power wiring harnesses are supplied attached to the interior left side panel of the UPM section see Figure 28 10 Locate...

Page 93: ...ee B in Figure 35 20 In the UPM section see B in Figure 35 locate the coiled RJ 45 CAN cable Remove the wire ties securing the cable to the interior left side panel of the UPM section Route this cable...

Page 94: ...74 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 31 ISBM Section Intercabinet Power Terminal Locations AC Input to ON OFF UPS System Installation...

Page 95: ...n a UPS without CB1 UPM input wiring terminations are in the same positions on the bus bars installed in the place of CB1 NOTE On a UPS configured as an IOM UPM input wiring terminations are the same...

Page 96: ...UPMs Cable 1G3 Black UPM 1 1E5A Cable 1G3 Black DC Input to UPM Cable 1G3 Red UPM 1 1E4A Cable 1G3 Red Cable 2G3 Black UPM 2 2E5A Cable 2G3 Black Cable 3G3 Black UPM 3 3E5A Cable 3G3 Black Cable 2G3 R...

Page 97: ...le 3G4 3G5 Orange UPM 1 Cable 1G4 1G5 Brown UPM 2 Cable 2G4 2G5 Brown UPM 3 Cable 3G4 3G5 Brown UPM 1 Cable 1G4 1G5 Yellow UPM 2 Cable 2G4 2G5 Yellow UPM 3 Cable 3G4 3G5 Yellow UPM 1 Cable 1G4 1G5 Gra...

Page 98: ...nterface Harness Locations Wiring Access Location of J50 J51 J61 and J70 Coiled Harnesses Location of RJ 45 Coiled CAN Cable UPM Wireway Location of P61 Harness Location of P50 P51 and P70 Harnesses U...

Page 99: ...on Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 79 Figure 36 Pl1 Interface Board Location Pl1 Interface Board Front ISBM Section Right Side Inside View UPS System Installat...

Page 100: ...alled proceed to paragraph 4 7 Distributed Bypass Tie Cabinet Installation if installing a distributed bypass tie cabinet otherwise proceed to paragraph 4 8 Installing UPS External and Battery Power W...

Page 101: ...up to remove them from the panel hanger brackets at the top of the cabinet 2 Remove the screws securing the top and bottom internal safety shield panels and remove the panels to gain access to the inp...

Page 102: ...bris Shields ISBM Section Front Ventilation Grill Debris Shields Remove shields before operating system Three UPM Section Front Two UPM Section Front Ventilation Grill Debris Shields Remove shields be...

Page 103: ...tion 5 Using hardware from the external wiring terminal hardware kit see Table 21 connect phase A B and C rectifier input power wiring from the utility source to the rectifier input terminals in the I...

Page 104: ...ph 3 2 4 UPS System Power Wiring Preparation for wiring and termination requirements 10 Proceed to paragraph 4 8 2 Battery Power Wiring 11 Using hardware from the external wiring terminal hardware kit...

Page 105: ...C E3 Phase B E2 AC Input to UPS Bypass Front Ground Terminals NOTE AC Input to Bypass terminals are not applicable to an IOM configuration Section A A 4 4 8 8 2 2 B Ba at tt te er ry y P Po ow we er...

Page 106: ...ng the UPS for a common battery proceed to Step 3 if wiring for a separate battery proceed to Step 5 3 Using hardware from the external wiring terminal hardware kit see connect the positive negative a...

Page 107: ...ert 9395P 900 Installation and Operation Manual 164000501 Rev 12 87 Figure 42 UPS Power Terminal Detail BB Common Battery DC Input from Battery E4 E5 DC Input from Battery Front Section B B UPS System...

Page 108: ...DC Input from Battery UPM 1 DC Input from Battery E4 UPM 2 DC Input from Battery E4 UPM 3 UPM 4 FI UPM UPM 4 FI UPM 4 4 9 9 I In ns st ta alllliin ng g I In nt te er rf fa ac ce e C Co on nn ne ec ct...

Page 109: ...mmunication bay To gain access to terminal block TB1 TB2 and the left interface entry conduit landing plates remove the screws securing the top internal safety shield panel and remove the panel Retain...

Page 110: ...90 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 44 ISBM Section Interface Terminal Locations UPS System Installation...

Page 111: ...al TB2 Name Description 1 Pull Chain Output Backup control for parallel operation 2 Pull Chain Common 3 Alarm Relay NC Output General purpose normally closed NC relay contact 4 Alarm Relay Common 5 Al...

Page 112: ...ogrammable UPS alarm activated by a remote dry contact closure Default function set for maintenance bypass 10 Building Alarm 5 Return NOTE Return indicates connection to electronics circuit ground Com...

Page 113: ...0 Vac and 28 Vdc NOTE Alarm relay normally open and normally closed return terminals are separated on the terminal board but are electrically in common NOTE Do not directly connect relay contacts to t...

Page 114: ...mum connected between the alarm input and common terminal as shown Building alarm inputs can be programmed for use with either normally open or normally closed contacts All control wiring and relay an...

Page 115: ...4 through Figure 49 NOTE When installing shunt trip and battery aux interface wiring to the UPS interface terminals conduit must be installed between the UPS and battery system 6 Remove the left inter...

Page 116: ...Vdc Battery Aux Battery Aux Return 48 Vdc Battery Shunt Trip NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG 48 Vdc Battery Shunt Trip TB1 UPS 5 6 7 8 ST ST ST ST 4 4 9 9 3 3 X...

Page 117: ...ure 44 and Figure 50 for X Slot communication bay locations 6 Close the door and secure the latch 7 Refer to the manual supplied with the X Slot card for operator instructions Figure 50 X Slot Communi...

Page 118: ...wiring must be in accordance with NEC Article 725 Class 2 requirements To Install a REPO switch 1 Verify the UPS system is turned off and all power sources are removed See Chapter 7 UPS Operating Inst...

Page 119: ...ening Torque 3 NO TB1 3 Twisted Wires 2 14 22 AWG 0 75 4 0 mm2 7 lb in 0 8 Nm 4 NO TB1 4 Figure 52 Normally Open REPO Switch Wiring 3 NO 1 NC UPS TB1 2 Return 4 Return REPO Switch NO Twisted Wires NOT...

Page 120: ...be a latching type switch not tied to any other circuits NOTE REPO normally open and normally closed return terminals are separated on the terminal board but are electrically in common UPS TB1 2 Retur...

Page 121: ...s other than verifying software and operating setup parameters Service personnel may request a copy of the completed Installation Checklist to verify all applicable equipment installations have been c...

Page 122: ...o A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the UPS and battery cabinet OPTIONAL o Accessories are mounted in installed locations and...

Page 123: ...ed to the UPS cabinets and to the tie cabinet or distribution panel o All power cables are properly sized and terminated o A ground conductor is properly installed o Controller Area Network CAN wiring...

Page 124: ..._____________________ _________________________________________________________________________ _________________________________________________________________________ ______________________________...

Page 125: ...or 5A maximum Power wiring should be a minimum of 22 AWG and a maximum of 14 AWG The wire should be rated for 1A minimum Use only 75 C copper wire 120 Vac for the RMP II RIM II or SCM II should be pro...

Page 126: ...erify the UPS system is turned off and all power sources are removed See Chapter 7 UPS Operating Instructionsfor shutdown instructions 2 Unfasten the front door latch and swing the door open see Figur...

Page 127: ...Bridge Card Interface Connections J3 Terminal Name Description 1 Alarm Programmable UPS alarm Activated by a remote dry contact closure 2 Alarm Return 3 Alarm Relay NC Normally closed contact opens w...

Page 128: ...ware for later use 4 Remove the interface entry conduit landing plates to drill or punch holes see Figure 39 5 Reinstall the interface entry plates and install the conduit 6 To locate the appropriate...

Page 129: ...ring without MOBs UPS 1 CAN Bridge Card J3 UPS 2 CAN Bridge Card J3 UPS 3 CAN Bridge Card J3 If Installed UPS 4 CAN Bridge Card J3 If Installed NOTE External CAN connections between UPSs require shiel...

Page 130: ...10 1 2 3 4 5 7 8 6 9 10 1 2 3 4 5 7 8 6 9 10 UPS 1 Twisted Pair Twisted Pair Twisted Pair Twisted Pair Twisted Pair Twisted Pair UPS 2 UPS 3 If Installed Twisted Pair UPS 4 If Installed TB1 TB1 1 B T...

Page 131: ...ted pair wire NOTE Use twisted pair wiring between the UPS and MOB AUX contacts NOTE Always m contact operation prior to wiring 2 S P U 1 S P U 2 B T 2 B 2 B T TB2 1 B T 1 B T UPS 3 If Installed UPS 4...

Page 132: ...ull Chain Common UPS 4 CAN Bridge Card J3 1 Alarm MOB 4 Aux 1 NC MOB Open Alarm UPS 4 CAN Bridge Card J3 2 Alarm Return MOB 4 Aux 1 Com UPS 4 TB2 1 Pull Chain MOB 4 Aux 2 NO Pull Chain MOB 1 Aux 2 Com...

Page 133: ...e 60 Figure 61 and Table 36 for the RMP II terminal location and wiring information NOTE 120 Vac for the RMP II should be supplied from the critical bus by facility planners or the customer 8 Install...

Page 134: ...a inverter or bypass If the indicators on the RMP II show the appropriate status then it is operating correctly If the communication link between the UPS and the RMP II is not present the RMP II perfo...

Page 135: ...on 7 Install wiring between the UPS and RIM II See Figure 56 and Table 32 for the Hot Sync CAN Bridge Card terminal location and wiring information and Figure 60 Figure 61 and Table 36for the RIM II t...

Page 136: ...l S Su up pe er rv viis so or ry y C Co on nt ta ac ct t M Mo od du ulle e I II I To install SCM II wiring 1 Verify the UPS system is turned off and all power sources are removed See Chapter 7 UPS Ope...

Page 137: ...and Table 36 for the terminal location and wiring information Figure 63 Supervisory Contact Module II Terminal Location Ground Terminal Terminal TB1 Signal Connections from the UPS Terminal TB3 120 V...

Page 138: ...n Imminent NOTE Supervisory contacts are rated at 2 0A at 28 Vdc or 120 Vac and 0 15A at 115 Vdc NOTE Supervisory contacts require an external power supply Internal 24 Vdc is not capable of supplying...

Page 139: ...emote Monitor Panel II Dimensions Flush Mount using 10 Pan Head Screws Mount with vent holes facing up Surface Mount using 10 Pan Head Screws for Hanging Mount with vent holes facing up Dimensions are...

Page 140: ...lay Interface Module II Dimensions Knockouts Provided on Five Surfaces Surface Mount using 10 Pan Head Screws for Hanging Mount with vent holes facing up Flush Mount using 10 Pan Head Screws Mount wit...

Page 141: ...rvisory Contact Module II Dimensions Surface Mount using 10 Pan Head Screws for Hanging Mount with vent holes facing up Flush Mount using 10 Pan Head Screws Mount with vent holes facing up Dimensions...

Page 142: ...122 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Installing Options and Accessories...

Page 143: ...r a specified period of time or until the utility power returns For extended power outages the UPS allows you to either transfer to an alternative power system such as a generator or shut down your cr...

Page 144: ...agement System VMMS mode the UPS operates as a traditional double conversion UPS but selectively shifts the load to fewer UPMs to increase the efficiency of the UPS In Bypass mode the critical load is...

Page 145: ...y returns to Online mode when the overload condition is cleared and system operation is restored within specified limits If the UPS suffers an internal failure it switches automatically to Bypass mode...

Page 146: ...is 80 of the UPM full power rating If the limit is exceeded additional UPMs take on the increased load The VMMS redundancy setting sets the number of redundant UPMs that the customer requires Both the...

Page 147: ...d protection contactor is normally always closed ready to support the static switch unless the bypass input source becomes unavailable Figure 70 Path of Current Through the UPS in Bypass Mode K1 K3 K5...

Page 148: ...peration the battery continues discharging until a DC voltage level is reached where the inverter output can no longer support the connected loads When this event occurs the UPS issues another set of...

Page 149: ...Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 129 Understanding UPS Operation...

Page 150: ...mon Rectifier Feed Common Battery Dual Feed Configuration Continuous Static Switch Figure 75 Eaton 9395P 900 900 Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 Single...

Page 151: ...Separate Battery IOM Configuration Figure 82 Eaton 9395P 900 900 Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 Single Reverse Transfer UPS Four UPM Common Rectifier...

Page 152: ...se Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output...

Page 153: ...ut Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 3 Battery Breaker E4 E5 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor...

Page 154: ...Interface Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fu...

Page 155: ...y Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier...

Page 156: ...3 or 4 Wire A B C Rotation Interface Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 B...

Page 157: ...rface Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse F...

Page 158: ...ilding Alarms Alarm Relays Fuse Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 1 Battery Breaker E4 E5 Batte...

Page 159: ...ery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifi...

Page 160: ...ice Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker BATTERY SYSTEM E4 E5 Battery Converter Inverter...

Page 161: ...e Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fus...

Page 162: ...tifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fus...

Page 163: ...y Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 1 Bypass Breaker CB4 Battery Converter Inverter Output Contacto...

Page 164: ...s If a bypass input breaker BIB is installed in the maintenance bypass and a single feed UPS is being installed a single feed to the maintenance bypass is acceptable for supplying both the UPS and the...

Page 165: ...2 0 if both UPMs in a system are required to support the load A parallel capacity system can also be redundant 2 1 as long as there is always one or more UPMs online than required to support the load...

Page 166: ...or distribution panel for parallel systems up to four modules The applied load is shared equally among the available UPMs in the system Figure 85 shows the path of electrical power through the paralle...

Page 167: ...the load If the load can be supported the system does not switch to bypass Figure 86 shows the path of electrical power through the parallel system when operating in Bypass mode In a distributed bypa...

Page 168: ...to bypass 6 6 4 4 4 4 B Ba at tt te er ry y M Mo od de e D Diis st tr riib bu ut te ed d B By yp pa as ss s The UPSs transfer to Battery mode automatically if a utility power outage occurs or if the u...

Page 169: ...the battery discharge the input power becomes available again the rectifier begins to supply DC current to the inverter At this point the UPS returns to Online mode If at any time during the battery d...

Page 170: ...ype Figure 88 Eaton 9395P 900 900 Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 Eaton 9395P 900 600 Eaton 9395P 900 600 Eaton 9395P 900 550 Eaton 9395P 900 500 Eaton...

Page 171: ...Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse E1 E2 E3 CB1 optional UPS 2 A B E4 E5 BATTERY SYSTEM Not supplied with the UPS C E9...

Page 172: ...Switch Fuse E1 E2 E3 CB1 optional UPS 2 A B E4 E5 BATTERY SYSTEM Not supplied with the UPS C E9 E10 E11 E12 D Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E...

Page 173: ...E12 D Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse E1 E2 E3 CB1 optional UPS 3 A B E4 E5 BATTERY SYSTEM Not supplied with the UP...

Page 174: ...154 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Understanding UPS Operation...

Page 175: ...s section of the manual and have thorough knowledge of UPS operation before attempting to operate any of the controls NOTE 3 The UPS displays two minutes of battery runtime at the initial startup Afte...

Page 176: ...d to control the AC input to the UPS rectifier 7 7 2 2 C Co ollo or r T To ou uc ch hs sc cr re ee en n C Co on nt tr ro oll P Pa an ne ell This section describes how the various screens are used to c...

Page 177: ...93 UPS Color Touchscreen Control Panel Typical 1 2 Symbols enlarged to show detail The color touchscreen control panel consists of A color liquid crystal touch screen display 1 A horizontal row of LED...

Page 178: ...tor is not illuminated when the system is in Bypass mode Red Lit Steady The UPS has an active alarm and requires immediate attention The screen shows the highest priority active alarms All alarms are...

Page 179: ...ystem model and time allows the operator select a different language from an imbedded list The top line of the display blinks while scrolling when the system needs attention Some notices and alarms ma...

Page 180: ...uest Screen A B C ENTER BUTTON Number indicates security level 0 4 Table 40 Security Levels and Functions Level Name Passcode Description 0 USER NONE USER 1 CONTROL 1111 USER CONTROL 2 CONFIGURATION 0...

Page 181: ...ontrol screens POWER MAPS Allows operator to observe system power flow LOGS Allows access to system information logs STATISTICS Allows access to see system specific operation values SETTINGS Allows ac...

Page 182: ...S Sc cr re ee en n O On nlliin ne e M Mo od de e Figure 97 shows the Main Menu and Power Maps screen The Power Maps screen displays immediately after entering the access code The Power Maps screen sh...

Page 183: ...gure 98 Output kVA Screen from Home Screen Touching the AVERAGE EFFICIENCY button displays the system efficiency screen shown in Figure 99 Figure 99 Average Efficiency Screen from Home Screen Touching...

Page 184: ...igure 101 shows the Bypass screen The Bypass screen displays only when the system is in Bypass mode The Bypass screen shows a real time graphical representation of the operating status Touching any of...

Page 185: ...rs Summary screen This screen allows selection of the various metering readout functions of Input Output and overall System status The three left items in the OVERVIEW section of the screen are not ac...

Page 186: ...pass and Output screens allow selection of the source UPS Metering mode Line to Line Line to Neutral and UPS details See Figure 104 Figure 104 Meters Selection Buttons Typical Line to Neutral Opens se...

Page 187: ...Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 167 Figure 105 Input Meters Screen UPS Operating Instructions...

Page 188: ...6 allows the operator to choose the individual source for system readings Figure 106 Select Source Screen Input Meters Detail Screen The Show Details button Figure 107 shows the Input Meters detail sc...

Page 189: ...he Metering Method Option screen The operator can select line to line or line to neutral monitoring values See Figure 108 Figure 108 Online Mode Metering Method Option Screen Bypass Meters Screen The...

Page 190: ...reen The Show Details button on the Bypass Mode Metering Method Option Screen allows the operator to select the metering method for either line to line or line to neutral monitoring values See Figure...

Page 191: ...he Output Meters Screen shown in Figure 111 displays values pertaining to the system output Figure 111 Output Meters Screen 7 7 3 3 9 9 B Ba at tt te er ry y M Me et te er rs s S Sc cr re ee en n Figu...

Page 192: ...taking place The horn cycles at a half second rate System Event Indicators The status indicators on the UPS control panel work with the event horn to let the operator know when the UPS is operating in...

Page 193: ...Manual 164000501 Rev 12 173 Figure 114 User Log Screen 1 2 Selecting an event opens the Event Detail screen shown in Figure 115 This screen details the specifics of the event for the user to see Figur...

Page 194: ...12 7 7 3 3 1 12 2 B Ba at tt te er ry y L Lo og g Figure 116 shows the Battery Log access screen Figure 116 Battery Log Screen Figure 117 shows the Battery Log Detail screen Figure 117 Battery Log De...

Page 195: ...OLS pushbutton on the main menu bar to display the System Status screen Online operation transfer to bypass UPM start up and shutdown and LOAD OFF commands are controlled through this screen In additi...

Page 196: ...Go to Load Off System Controls Home Module Controls Controls EAA UPS STATUS STATUS BYPASS Available Online Online POWER XPERT 9395P Figure 121 shows the Module Controls screen This screen allows cont...

Page 197: ...evious screen Figure 121 the user can observe full details of an individual module It also allows the user to move through various modules and modes while within this screen The color of the UPM butto...

Page 198: ...stalled firmware version etc Touching the CLEAN SCREEN button disables the screen for 30 seconds to allow the user to safely clean the screen without affecting operation Figure 123 Settings Screen 7 7...

Page 199: ...wn in Figure 125 allows the operator to activate the various energy saving and power efficiency modes of the system The various Energy Advantage Architecture operations are described in the UPS Instal...

Page 200: ...allation and Operation Manual 164000501 Rev 12 Figure 126 Disable ESS Screen The screen shown in Figure 127 asks the operator if they want to start the High Alert mode timer Figure 127 High Alert Time...

Page 201: ...ure 128 allows the operator to query the system for various operational statistics such as shown in Figure 129 Figure 128 Statistics Basic Screen Figure 129 Statistics Data Detail Screen 7 7 3 3 1 18...

Page 202: ...Mo od du ulle e M Ma ap p S Sc cr re ee en n The screen shown in Figure 131 allows the operator to control the individual UPMs Figure 131 UPS Module Map Screen 7 7 3 3 2 20 0 S Sy ys st te em m O Ov...

Page 203: ...security level sign in If a sign in request screen appears see Figure 95 for details NOTE A Field Installed UPM FI UPM is always designated as UPM 4 7 7 4 4 1 1 S St ta ar rt tiin ng g t th he e U UP...

Page 204: ...the screen The UPM status indicates Active Charger ON on the UPM Module Control Detail screen see Figure 121 To activate or enable disable any of the UPS operational modes follow the online screen pro...

Page 205: ...r rg gy y S Sa av ve er r S Sy ys st te em m H Hiig gh h A Alle er rt t M Mo od de e NOTE 1 The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service En...

Page 206: ...g ge em me en nt t S Sy ys st te em m M Mo od de e To disable Variable Module Management System mode NOTE 1 The Variable Module Management System mode commands are displayed only if enabled at the fac...

Page 207: ...hock If the inverter output of the UPS is not available and the critical load needs to be energized In Bypass mode the critical load is not protected from commercial power interruptions and abnormalit...

Page 208: ...ive indicating logic power 8 Make sure you are logged in for user access see Figure 95 9 Verify no alarms are active 10 Press the Controls button on the Home screen see Figure 96 The System Status scr...

Page 209: ...dicating logic power 9 Make sure you are logged in for user access see Figure 95 10 Press the Controls button on the Home screen see Figure 96 The System Status screen is displayed see Figure 119 11 O...

Page 210: ...r f fr ro om m B By yp pa as ss s t to o O On nlliin ne e M Mo od de e To transfer the critical load to Online mode 1 If not already closed close the battery breaker 2 Make sure you are logged in for...

Page 211: ...8 Verify the following UPM x IS SHUTTING DOWN message appears The UPM POWER STATUS shows Shutdown on the Module Control Detail screen see Figure 122 The UPM status bar shows in a black color Shutdown...

Page 212: ...al load is lost when the Load Off is selected in the following step You should use this feature only when you want to de energize the critical load 3 Press the Load Off button The Shut Down confirmati...

Page 213: ...ass backfeed contactors open the battery breaker or disconnect is tripped and the power module is turned off immediately without asking for verification Do not attempt to restart the system after the...

Page 214: ...ib bu ut te ed d B By yp pa as ss s S Sy ys st te em m iin n O On nlliin ne e M Mo od de e To start the distributed bypass system If required to close a circuit breaker inside a UPS use appropriate pe...

Page 215: ...ve er r S Sy ys st te em m M Mo od de e To enable Energy Saver System mode NOTE 1 The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service En...

Page 216: ...AA screen is displayed see Figure 125 4 On the EAA screen select Start High Alert Timer the Start high alert timer confirmation screen appears see Figure 127 5 Select Yes on the confirmation screen Th...

Page 217: ...indicator is illuminated The UPS status indicates Online 7 7 5 5 7 7 S St ta ar rt t V Va ar riia ab blle e M Mo od du ulle e M Ma an na ag ge em me en nt t S Sy ys st te em m H Hiig gh h A Alle er rt...

Page 218: ...icating logic power 11 Make sure you are logged in for user access see Figure 95 12 On any UPS press the Controls button on the Home screen see Figure 96 The System Status screen is displayed see Figu...

Page 219: ...dule Controls Detail screen for the UPM appears see Figure 122 14 Press the Start UPM button in the Power Status section 15 Select Yes on the confirmation screen Verify the following A message that th...

Page 220: ...ation screen Verify the following message is displayed UPM 1 IS STARTING The UPM 1 rectifier and inverter turn on UPM Power Status line shows idle The UPM status bar shows in a gray color Idle 16 Repe...

Page 221: ...as ss s M Mo od de e a an nd d S Sh hu ut t D Do ow wn n U UP PM Ms s To transfer the critical load to Bypass mode and shut down all UPMs 1 Transfer the critical load to bypass by performing the proc...

Page 222: ...graph 5 1 Installing an Optional Hot Sync CAN Bridge Card To shut down a single UPS 1 Open the MOB for the UPS being shut down 2 Make sure you are logged in for user access see Figure 95 3 On the UPS...

Page 223: ...ser access see Figure 95 3 On the UPS to shut down press the Controls button on the Home screen see Figure 96 The System Status screen is displayed see Figure 119 4 On the System Status screen select...

Page 224: ...e equipment Injury to personnel may occur from electrical shock 1 Close the MOB for the UPS being restarted 2 Close UPS input and bypass feeder circuit breakers for the UPS being restarted 3 Unfasten...

Page 225: ...n paragraph 7 4 17 Using the UPS Load Off Button UPS and Critical Load Shutdown The input output battery and bypass backfeed contactors open and the power module is turned off Power is present inside...

Page 226: ...lowing step You should use this feature only when you want to de energize the critical load 3 Press the Load Off button The Shut Down confirmation screen is displayed providing a choice to proceed or...

Page 227: ...the REPO pushbutton switch 1 Firmly push the red pushbutton until it locks into place The switch latches into the activated state see Figure 133 The input output and bypass backfeed contactors open th...

Page 228: ...n Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 134 REPO Operation Activated Pushbutton locked into place Deactivated Unlock pushbutton to release UPS Operating Instr...

Page 229: ...network drop Modbus Card provides direct integration of UPS information meters and status to a Building Management System BMS using the Modbus RTU protocol Relay Interface Card AS 400 has isolated dry...

Page 230: ...eway UPS card PredictPulse uses standard Eaton connectivity hardware requiring no special software devices only need to be connected to a network Ability to give an unlimited number of coworkers acces...

Page 231: ...ironments The software s mass configuration capabilities make installation and maintenance easy which minimizes the effort required and benefits the bottom line Eaton s cost effective Intelligent Powe...

Page 232: ...RMP II can be installed to monitor the operation of the UPS system from virtually any location within the facility up to 150m 500 ft from the UPS The RMP II contains backlit status indicators and a lo...

Page 233: ...supplying the critical load Usually this means that the UPS is not energized The load is not protected in Bypass mode and a horn sounds after 30 seconds UPS ALARM The UPS system is issuing an alarm Co...

Page 234: ...connectors labeled J1 through J4 Figure 137 Relay Interface Module II The RIM II can provide the status and alarm signals shown in Table 43 Table 43 Customer Interface Connectors Status J1 through J4...

Page 235: ...flush mounted or surface mounted on a desktop or secured to a wall Figure 138 shows the SCM II Figure 138 Supervisory Contact Module II The SCM II provides signals for the indications shown in Table...

Page 236: ...216 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Communication...

Page 237: ...e any assumptions about the electrical state of any cabinet in the UPS system AVERTISSEMENT L installation et l entretien ne doivent tre effectu s que par du personnel qualifi PR SENCE DE TENSIONS MOR...

Page 238: ...nsiderations and Chapter 10 Product Specifications 4 Ensure the UPS is in Online mode Online status indicator is illuminated If an alarm lamp is illuminated or the Online status indicator is not illum...

Page 239: ...am filters over the screw heads on the cabinet mounted studs and remove the filters from the cabinet e Push the washed or new foam filters over the screw heads on the cabinet mounted studs until seate...

Page 240: ...cement filter To remove the filter a Remove one top screw and two bottom screws securing the FI UPM front panel refer to the Eaton Power Xpert 9395P UPS Field Installed UPM Mechanical Installation Man...

Page 241: ...ents wiring and connections exhibit evidence of overheating Particular attention should be given to bolted connections Maintenance procedures should specify that the bolted connections be retorqued to...

Page 242: ...r fire Observe proper precautions ATTENTION Une batterie peut pr senter un risque de choc lectrique de brulure ou d incendie Suivre les pr cautions qui s imposent Pour le remplacement utiliser le m me...

Page 243: ...50 60 Hz Eaton 9395P 900 550 two or three UPM 550 kVA 500 kW 50 60 Hz Eaton 9395P 900 500 two or three UPM 500 kVA 500 kW 50 60 Hz Eaton 9395P 900 450 two or three UPM 450 kVA 450 kW 50 60 Hz 1 10 0 2...

Page 244: ...15 or Figure 16 for 415V three UPM models See Figure 17 or Figure 18 for 400V three UPM models See Figure 19 or Figure 20 for 380V three UPM models Output Voltage Balance 2 5 for 100 maximum load imb...

Page 245: ...0 m 3000 ft at 40 C without derating Storage Temperature 25 to 60 C excluding batteries prolonged storage above 40 C causes rapid battery self discharge Relative Humidity Operating and Storage 5 to 95...

Page 246: ...16400050112 164000501 12...

Reviews: