9395P-900 Installation and Operation Manual 164000501—Rev 12
183
Figure 132. System Overview Screen
77..44
S
Siinnggllee U
UP
PS
S O
Oppeerraattiioonn
The paragraphs in this section provide operating instructions for a UPS system containing only one UPS.
NOTE
If the touch screen fails to respond, open the front door and depress the RESET button
located on the bottom of the screen mounting assembly. The screen will reboot but
NOT affect system status or operation.
NOTE
Some UPS operations may require a security level sign-in. If a sign-in request screen
appears, see
for details.
NOTE
A Field Installed UPM (FI-UPM) is always designated as UPM 4.
77..44..11
S
Sttaarrttiinngg tthhee U
UP
PS
S iinn O
Onnlliinnee M
Mooddee
To start the UPS system:
If required to close a circuit breaker inside a UPS, use appropriate personal protective equipment. Injury to
personnel may occur from electrical shock.
1.
Unfasten the front door latch and swing the door open (see
).
NOTE
*Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see
).
2.
*Verify that input breaker CB1 is open.
3.
Close the UPS input feeder circuit breaker.
4.
Close the UPS Bypass input feeder circuit breaker.