220
Eaton
®
Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
Figure 140. FI-UPM Air Filter Location
UPM Air Filters
3.
If the UPS is a four UPM model, check the Field Installed UPM (FI-UPM) air filter (located behind the front
panel) and wash or replace as necessary. See
for the filter location. The FI-UPM filter size is 20"
x 44" x 0.25". Contact an Eaton service representative for a replacement filter. To remove the filter:
a.
Remove one top screw and two bottom screws securing the FI-UPM front panel (refer to the
Eaton
®
Power Xpert
®
9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503)).
listed in
para
). Lift the panel straight up to remove it from the panel hanger bracket at
the top of the cabinet.
b.
Pull the foam filter over the screw heads on the cabinet mounted studs and remove the filter from the
cabinet.
Verify washed filter is thoroughly dry before reinstalling.
ATTENTION!
Vérifier que les filtres sont bien secs avant de les réinstaller.