1100..22..22 U
UP
PS
S O
Ouuttppuutt
UPS Output Capacity
100% rated current
Output Voltage Regulation
±1.5% (10% to 100% load)
Output Voltage Adjustment
(N/ 3%)
480 Vac nominal, adjustable from 466 Vac to 494 Vac
Output Voltage Harmonic Content
1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See
or
for 480V three UPM models.
See
or
for 480V two UPM models.
See
or
for 415V three UPM models.
See
or
for 400V three UPM models.
See
or
for 380V three UPM models.
Output Voltage Balance
2.5% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement
±4° for 100% maximum load imbalance (linear load)
Output Transients
Meets Class 1 IEC 62040-3 (10% to 100% load)
Frequency Regulation
±0.1 Hz free running
Synchronous to Bypass
+10% to -10%
Frequency Slew Rate
.7 Hz per second maximum
Load Compatibility
0.9 pF Leading
0.8 pF Lagging
Overload Capability
110% for 10 minutes
125% for 120 seconds
150% for 15 seconds
NOTE
The 125% and 150% overloads are based on the non-derated hardware capability of the
UPS.