9395P-900 Installation and Operation Manual 164000501—Rev 12
225
1100..22..33 U
UP
PS
S EEnnvviirroonnm
meennttaall
Operating Temperature
All ratings except 900 kW: 0 to 40°C (32 to 104°F) without derating.
For 900 kW, 900 kW: 0 to 35°C at elevation up to 1000m without derating.
The recommended operating temperature is 25°C (77°F).
Operating Altitude
Maximum 1000 m (3000 ft) at 40°C without derating
Storage Temperature
–25 to +60°C, excluding batteries (prolonged storage above 40°C causes rapid
battery self discharge)
Relative Humidity (Operating and Storage)
5% to 95% maximum non-condensing
Acoustical Noise
78 dB at a 1m distance, A weighted for one UPM UPS
81 dB at a 1m distance, A weighted for two UPM UPS
EMI Suppression
Meets IEC 62040-2, category C3
Electrostatic Discharge (ESD) Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without damage
and with no disturbance or adverse effect to the critical load.