9395P-900 Installation and Operation Manual 164000501—Rev 12
19
•
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
•
The cabinet can be installed in
line-up-and-match
or
standalone
configurations.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in
and the size
requirements shown in
through
. Dimensions are in millimeters (inches).
does not include the weight of the Field Installed UPM (FI-UPM). For FI-UPM weights and dimensions,
refer to the
Eaton 9395P Field Installed UPM Mechanical Installation Manual (P-164000503)
, listed in paragraph
Includes the weights of the heaviest cabinet configuration. Actual weights may be less due to installed
configuration. Weights are in kilograms (pounds).
Table 2. UPS Cabinet Maximum Weights
Model
Section
Maximum Weight kg (lb)
Shipping
Installed
Eaton 9395P-900/900*
Eaton 9395P-900/900
Eaton 9395P-900/825
Eaton 9395P-900/750
Eaton 9395P-900/675
ISBM (CSS)
808 (1782)
764 (1684)
3XUPM
496 (1094)
475 (1047)
FI-UPM
496 (1094)
764 (1684)
Eaton 9395P-900/600*
Eaton 9395P-900/600
Eaton 9395P-900/550
Eaton 9395P-900/500
Eaton 9395P-900/450
ISBM (CSS)
808 (1782)
764 (1684)
2XUPM
1152 (2541)
1125 (2418)
NOTE CSS = Continuous Static Switch
NOTE CSS =
describes power ratings of each model.
The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in
. Dimensions are in
millimeters (inches).
Table 3. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18") minimum clearance for ventilation
From Front of Cabinet
1067mm (42") working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
•
For all ratings except 900 kW, 600 kW: 0 to 40°C (32–104°F) at elevations up to 1000m without derating