Eaton
®
Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
49
Table 20. UPS External Power Cable Terminations for Three/Four UPM Models (Continued)
Terminal Function
Terminal
Function
Bus Landings (using
both sides of bus)
Tightening Torque
Nm (lb ft)
Bolt Size
Customer Ground
Ground
Ground
15 – 2 bolt mounting
76 (56)
M12
NOTE
Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in
.
NOTE
Bypass terminations are not applicable to IOM configurations.
Table 21. Supplied External Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Bolt, Grade 5
M12 x 40 mm
30
Ground and Neutral
180190078-112
Bolt, Grade 5
M12 x 50 mm
86
Rectifier Input, Bypass Input, Battery Input, and
Output
180190078-115
Flat Washer
M12
202
Rectifier Input, Bypass Input, Battery Input,
Output, and Ground
180500036-120
Conical
Washer
M12
116
Rectifier Input, Bypass Input, Battery Input,
Output, and Ground
180500037-120
Nut
M12
86
Rectifier Input, Bypass Input, Battery Input,
Output, and Ground
180200001-07
NOTE Bypass terminations are not applicable to IOM configurations.
Table 22. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part
Size
Quantity
Manufacturer
Part Number
Notes
Long Barrel 2-Hole Lug
2/0 AWG
As required
Thomas & Betts
54862BE
Copper wire only
3/0 AWG
Thomas & Betts
54864BE
4/0 AWG
Thomas & Betts
54866BE
250 MCM
Thomas & Betts
54868BE
300 MCM
Thomas & Betts
54870BE
350 MCM
Thomas & Betts
54872BE
400 MCM
Thomas & Betts
54874BE
500 MCM
Thomas & Betts
54876BE
Manual Hydraulic Crimp Tool
14 Ton
1
Thomas & Betts
TBM14M
Die Set
N/A
1
Thomas & Betts
15506
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See
for conduit
requirements.
Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit.
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground
conductor sized in accordance with NEC Table 250.122.
Conduit sizes listed are for copper wiring only.