9395P-900 Installation and Operation Manual 164000501—Rev 12
53
Table 25. 400V/380V Power Cable Conduit Requirements (Continued)
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
Number of
Conduits
(A, B, C, Ground)
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
6
3
6
Eaton 9395P-900/450
See Note 1
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
4
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
6
3
6
All models
DC
(Separate
Battery -
per UPM)
Battery
(Positive, Negative, Ground)
7
4
1
NOTE 1 Because of the future upgradability to a fully rated 400V/380V 825 kVA UPS with the addition of the FI-UPM, these conduit
sizes are specified for an 825 kVA UPS.
NOTE 2 Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing
: Refer to the notes at the bottom of
to
Input/Output Ratings and External Wiring
Requirements.
External overcurrent protection and disconnect are not provided by this product, but are required by codes.
Refer to Refer to
to
for wiring requirements. If an output lockable disconnect is required, it is
to be supplied by the customer.
lists the recommended rating for 480V, 415V, 400V, and 380V input circuit breakers with 80 and 100%
breaker ratings for rectifier input.
NOTE
For the 9395P-900 400/415/380V models, the max output is 825 kW/ 825 kVA.
Table 26. Recommended Input Circuit Breaker Ratings (100% and 80% Load Rating)
UPS Model
Input Rating
%
480V
415V
400V
380V
Eaton 9395P-900/900
100
1600A
N/A
N/A
N/A
80
2000A
N/A
N/A
N/A
Eaton 9395P-900/825
100
1600A
1600A
1600A
1600A
80
1600A
2000A
2000A
2000A
Eaton 9395P-900/750
100
1200A
1600A
1600A
1600A
80
1600A
2000A
2000A
2000A