9395P-900 Installation and Operation Manual 164000501—Rev 12
55
Table 27. Recommended Bypass, Output, and MOB Circuit Breaker Ratings (100% and 80% Load Rating)
UPS Model
Input Rating
%
480V
415V
400V
380V
Eaton 9395P-900/900
100
1200A
N/A
N/A
N/A
80
1600A
N/A
N/A
N/A
Eaton 9395P-900/825
100
1000A
1200A
1200A
1600A
80
1600A
1600A
1600A
1600A
Eaton 9395P-1200/750
100
1000A
1200A
1200A
1200A
80
1200A
1600A
1600A
1600A
Eaton 9395P-1200/675
100
1000A
1000A
1000A
1200A
80
1200A
1200A
1600A
1600A
Eaton 9395P-1200/600
100
800A
1000A
1000A
1000A
80
1000A
1200A
1200A
1200A
Eaton 9395P-900/550
100
700A
800A
800A
1000A
80
1000A
1000A
1000A
1200A
Eaton 9395P-900/500
100
700A
700A
800A
800A
80
800A
1000A
1000A
1000A
Eaton 9395P-900/450
100
600A
700A
700A
700A
80
700A
800A
1000A
1000A
Eaton 9395P-900/400
See Note
100
500A
600A
600A
700A
80
600A
700A
800A
800A
NOTE Because of the future upgradability to a fully rated 900 kW UPS with the addition of the FI-UPM, Eaton recommends
using the breaker size specified for a 1100 kW UPS.
There is no manual DC disconnect device within the UPS.
A battery disconnect switch is required for battery systems and may also be required by NEC or local codes.
The battery disconnect switch should be installed between the battery and the UPS.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is
computed at 2 volts per cell.
The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of
nominal DC voltage at rated battery current.
External DC input overcurrent protection and disconnect switch is to be provided by the customer.
and
list the maximum ratings for continuous–duty rated circuit breakers satisfying the criteria for both.
Recommended disconnect size is based on a maximum full load discharge time less than 3 hours. For longer
discharge times a larger disconnect may be required.