56
Eaton
®
Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
Table 28. Recommended DC Input Battery Disconnect Ratings – Common Battery
UPS Model
Input Rating
480V
Eaton 9395P-900/900*
Eaton 9395P-900/900
Eaton 9395P-900/825
2500A
Eaton 9395P-900/750
Eaton 9395P-900/675
2000A
Eaton 9395P-900/600*
Eaton 9395P-900/600
Eaton 9395P-900/550
Eaton 9395P-900/500
Eaton 9395P-900/450
See Note 1
2500A
NOTE Because of the future upgradability to a fully rated 900 kVA UPS with the addition of the FI-UPM, these breaker sizes are
specified for a 900 kVA UPS.
Table 29. Recommended DC Input Battery Disconnect Ratings – Separate Battery
UPS Model
Input Rating for Each UPM
480V
Eaton 9395P-900/900*
Eaton 9395P-900/600*
800A
Eaton 9395P-900/900
Eaton 9395P-900/825
Eaton 9395P-900/750
Eaton 9395P-900/675
Eaton 9395P-900/600
Eaton 9395P-900/550
Eaton 9395P-900/500
Eaton 9395P-900/450
700A
NOTE Because of the future upgradability to a fully rated 900 kVA UPS with the addition of the FI-UPM, these breaker sizes are
specified for a 900 kVA UPS.
33..22..55
U
UP
PS
S S
Syysstteem
m IInntteerrffaaccee W
Wiirriinngg P
Prreeppaarraattiioonn
Control wiring for features and options should be connected at the customer interface terminal blocks located
inside the UPS.
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
AVERTISSEMENT!
Ne pas directement brancher les contacts de relais aux circuits du réseau. Une isolation renforcée des réseaux
est nécessaire.