Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
S
164201687 Rev 4
www.eaton.com/powerquality
2-1
Chapter 2
Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of
the batteries. Please read all instructions before operating the equipment and save this manual for future
reference.
The battery cabinet is designed for industrial or computer room applications and should be handled with
appropriate care.
D
A
N
G
E
R
This battery cabinet contains
LETHAL VOLTAGES
. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY
. There are
NO USER SERVICEABLE PARTS
inside the
battery cabinet.
W
A
R
N
I
N
G
S
This battery cabinet contains its own energy source. The internal wiring and output terminals may carry
live voltage even when the UPS is not connected to an AC source.
S
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled,
indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40
C
(104
F). Do not operate near water or excessive humidity (95% maximum). The system is not intended for
outdoor use.
S
Ensure all power is disconnected before performing installation or service.
S
Batteries can present a risk of electrical shock or burn from high short‐circuit current. The following
precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with
insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Wear rubber globes and boots.
S
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter
wiring can cause injury.
S
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
C
A
U
T
I
O
N
S
Installation or servicing should be performed by qualified service personnel knowledgeable of batteries
and required precautions. Keep unauthorized personnel away from batteries. Consider all warnings,
cautions, and notes before installing or replacing batteries. DO NOT DISCONNECT the batteries while the
UPS is in Battery mode.
S
Replace batteries with the same number and type of batteries as originally installed in the battery
cabinet.
S
Disconnect the charging source prior to connecting or disconnecting terminals.
S
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contacting
any part of a grounded battery can cause a risk of electric shock. An electric shock is less likely if you
disconnect the grounding connection before you work on the batteries.
S
Proper disposal of batteries is required. Refer to local codes for disposal requirements.
S
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
S
Keep the battery cabinet doors closed to ensure proper cooling airflow and to protect personnel from
dangerous voltages inside the unit.
S
Do not install or operate the battery cabinet close to gas or electric heat sources.
Figure