INSTALLATION
Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
S
164201687 Rev 4
www.eaton.com/powerquality
4-6
Ground Wire
Ground Studs
Existing Hinge
Existing Hinge
Battery Cabinet 1
Battery Cabinet 2
Front View
Bracket from Kit
Nuts from Kit
ÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒ
Top View
Figure 4‐4. Battery Cabinet Bottom Joining Brackets and Ground Wire
11.
Secure the bracket to the hinges with hardware from the field kit.
12.
Route the ground wire (from the field kit) from the ground stud in one battery
cabinet, under the lower battery tray and through the cabinet-to-cabinet cable
access area in the side of the cabinets, and attach to the ground stud in the other
battery cabinet (see Figure 4‐4). Hardware is provided on each ground stud.
13.
If installing additional battery cabinets, repeat Steps 4 through 12 to join each
additional battery cabinet; otherwise, proceed to Step 14.
14.
If not already installed, mount the hanger brackets to the top appropriate side of
the last battery cabinet using M4 screws (see Figure 4‐5).
15.
If not already installed, hang the side panel on the hanger brackets and align with
the front and rear of the battery cabinet.
16.
If not already secured, secure the side panel at the bottom using M4 hex-head
screws previously removed.