INSTALLATION
Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
S
164201687 Rev 4
www.eaton.com/powerquality
4-7
Hanger Bracket Location
(secured with screws)
Figure 4‐5. Battery Cabinet Hanger Bracket Location
4.3.2
External Power Wiring Installation
NOTE
The battery cabinet is shipped with a debris shield covering the ventilation grill on top of the unit. Do
not remove the debris shield until installation is complete. However, remove the shield before using the
battery cabinet. Once the debris shield is removed, do not place objects on the ventilation grill.
NOTE
Remove the battery cabinet top or bottom conduit landing plate to drill or punch conduit holes (see
NOTE
Wiring is installed externally between each battery cabinet and the UPS or battery disconnect using
conduit (see Figure 5‐1 through Figure 5‐4).
NOTE
All battery cabinets have to be directly connected to the UPS or battery disconnect, not daisy-
chained through each cabinet. All power wiring between the UPS and/or battery disconnect is customer
supplied.
To install wiring connections:
D
A
N
G
E
R
LETHAL VOLTAGE
is present when performing the remaining steps in this section and subsequent
sections.
C
A
U
T
I
O
N
The 1085
and
1085HR
battery cabinets CANNOT be intermixed. Serious damage to equipment may result.