MAINTENANCE
Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
S
164201687 Rev 4
www.eaton.com/powerquality
6-2
6.2
Performing Preventive Maintenance
The battery cabinet requires very little preventive maintenance. However, the battery
system should be inspected periodically to verify that the units are operating normally
and that the batteries are in good condition.
6.2.1
DAILY Maintenance
Perform the following steps daily:
1.
Check the area surrounding the battery cabinet. Ensure the area is not cluttered,
allowing free access to the unit.
2.
Ensure the air intakes (vents on the front doors) and exhaust opening (on top of
the battery cabinet) are not blocked.
3.
Ensure the operating environment is within the parameters specified in
paragraph 3.2.1.
6.2.2
BATTERY Maintenance
Contact your service representative for battery maintenance. Battery replacement and
maintenance should be performed only by authorized service personnel.
6.3
Installing Batteries
C
A
U
T
I
O
N
The 1085
and
1085HR
batteries CANNOT be intermixed. Serious damage to equipment may result.
NOTE
There is no manual DC disconnect device within the UPS.
Contact your service representative for battery maintenance. Battery replacement and
maintenance should be performed only by authorized service personnel. Install
batteries in accordance with the battery and battery cabinet or battery rack
manufacturer's instructions.
6.4
Recycling the Used Battery or UPS
Contact your local recycling or hazardous waste center for information on proper
disposal of the used battery or UPS.
W
A
R
N
I
N
G
S
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is
required. Refer to your local codes for disposal requirements.
S
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It
may be toxic.
S
A battery can cause electrical shock, burn from high short‐circuit current, or fire. Observe proper
precautions.