INSTALLATION PLAN AND UNPACKING
Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
S
164201687 Rev 4
www.eaton.com/powerquality
3-2
The battery equipment operating environment must meet the weight requirements
shown in Table 3‐1 and the size requirements shown in Figure 3‐1 through Figure 3‐4.
The weight shown in Table 3‐1 is the maximum weight of a fully configured cabinet.
The weight of your cabinet may be less due to its configuration.
Table 3‐1. Battery Cabinet Weights
Model
Weight
kg (lb)
Shipping
Installed
Point Loading
Power Xpert 9395 1085 or 1085HR
with 40 batteries (480 Vdc)
2211 (4875)
2177 (4800)
8 at 272 (600)
The battery cabinet uses convection air cooling to regulate internal component
temperature. Air inlets are in the front of the cabinet and outlets are in the top. Allow
clearance in front of and above each cabinet for proper air circulation. The clearances
required around the battery cabinet are shown in Table 3‐2. Dimensions are in
millimeters (inches).
Table 3‐2. UPS Cabinet Clearances
From Top of Cabinet
Minimum clearance over the UPS cabinet is 457.2 mm (18
”
) for ventilation
From Front of Cabinet
914.4 mm (36
”
) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
The basic environmental requirements of both Models IBC-S and IBC-L for operation
of the battery system are:
S
Operational Temperature Range: 22-28°C (72-82°F)
S
Maximum Relative Humidity:
95%, noncondensing.
C
A
U
T
I
O
N
It is recommended for optimal battery life and discharge performance to keep the ambient air temperature
the battery is used in at 25°C (77°F). Operating temperatures above the recommended range will result in
decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's
Terms
and Conditions of Sale with Battery Replacement Coverage
and the
Battery Replacement Price Book
for more
information. These documents can be found at www.eaton.com/powerquality or contact your service